NFC34-125 BS AAC ACSR AAAC overhead line bare Conductor

Port: | Qingdao |
Payment Terms: | L/C,T/T,Western Union |
Supply Ability: | 150 Kilometer/Kilometers per Month |
Place of Origin: | Henan China |
Brand Name: | Hongda |
Model Number: | AAAC |
Insulation Material: | Bare |
Application: | Overhead |
Conductor Material: | Aluminum |
Jacket: | Bare |
Standard: | BS IEC ASTM DIN |
Delivery Detail: | Shipped in 10 days after payment |
Packaging Detail: | Wooden Drum |
AAAC (All Aluminum Alloy Conductor) referred to have higher strength but lower conductivity than pure aluminum. Being lighter, alloy conductors can sometimes be used to advantage in place of the more conventional ACSR;
Having lower breaking loads than the latter, their use becomes particularly favourable when ice and win loadings are low.
We can supply this conductor according to different recognized standards, such as BS EN50182, IEC61089, ASTM B399DIN 48, customer special specification also can be satisfied.
Applications:
Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics. Aluminum-alloy gives 6201-T81 gives AAAC higher resistance to corrosion than ACSR.
ALUMINIUM ALLOY CONDUCTOR ASTM B399 | |||||||||
Code Name | Area | Size&Stranding of ACSR with equal diameter | No. and diameter | Overall diameter | Weight | Nominal breaking load | MAX .DC resistance at 20℃ | ||
Nominal | Actual | AWG or MCM | Al/St | ||||||
MCM | mm2 | mm | mm | kg/km | kN | ohm/km | |||
AKRON | 30.58 | 15.48 | 6 | 6/1 | 7/1.68 | 5.04 | 42.7 | 4.92 | 0.3966 |
ALTON | 48.69 | 24.71 | 4 | 6/1 | 7/2.12 | 6.35 | 68 | 7.84 | 0.3811 |
AMES | 77.47 | 39.22 | 2 | 6/1 | 7/2.67 | 8.02 | 108 | 12.45 | 0.3671 |
AZUSA | 123.3 | 62.38 | 1/0 | 6/1 | 7/3.37 | 10.11 | 172 | 18.97 | 0.3524 |
ANAHEIM | 155.4 | 78.65 | 2/0 | 6/1 | 7/3.78 | 11.35 | 217 | 23.93 | 0.3448 |
AMHERST | 195.7 | 99.22 | 3/0 | 6/1 | 7/4.25 | 12.75 | 273 | 30.18 | 0.3375 |
ALLIANCE | 246.9 | 125.1 | 4/0 | 6/1 | 7/4.77 | 14.31 | 345 | 38.05 | 0.3306 |
BUTTE | 312.8 | 158.6 | 266.8 | 26/7 | 19/3.26 | 16.3 | 437 | 48.76 | 0.3196 |
CANTON | 394.5 | 199.9 | 366.4 | 26/7 | 19/3.66 | 18.3 | 551 | 58.91 | 0.3124 |
CAIRO | 465.4 | 235.8 | 397.5 | 26/7 | 19/3.98 | 19.88 | 650 | 69.48 | 0.3071 |
DARIEN | 559.5 | 283.5 | 477 | 26/7 | 19/4.36 | 21.79 | 781 | 83.52 | 0.3014 |
ELGIN | 652.4 | 330.6 | 556.5 | 26/7 | 19/4.71 | 23.54 | 911 | 97.42 | 0.2966 |
FLINT | 740.8 | 375.3 | 636 | 26/7 | 37/3.59 | 25.16 | 1035 | 108.21 | 0.2917 |
GREELY | 927.2 | 469.8 | 795 | 26/7 | 37/4.02 | 28.14 | 1295 | 135.47 | 0.2846 |
ALUMINIUM ALLOY CONDUCTOR BSEN50183 | |||||||
Code Name | Calculated Area | No. Of Wires | Diameter | Weight | Rated Strength | MAX .DC resistance at 20℃ | |
Wire | Cond. | ||||||
mm2 | mm | mm | kg/km | Kn | ohm/km | ||
Box | 18.8 | 7 | 1.85 | 5.55 | 51.4 | 5.55 | 1.748 |
Acacia | 23.8 | 7 | 2.08 | 6.24 | 64.9 | 7.02 | 1.3828 |
Almond | 30.1 | 7 | 2.34 | 7.02 | 82.2 | 8.88 | 1.0926 |
Cedar | 35.5 | 7 | 2.54 | 7.62 | 96.8 | 10.46 | 0.9273 |
Deodar | 42.2 | 7 | 2.77 | 8.31 | 115.2 | 12.44 | 0.7797 |
Fir | 47.8 | 7 | 2.95 | 8.85 | 130.6 | 14.11 | 0.6875 |
Hazel | 59.9 | 7 | 3.3 | 9.9 | 163.4 | 17.66 | 0.5494 |
Pine | 71.6 | 7 | 3.61 | 10.8 | 195.6 | 21.14 | 0.4591 |
Holly | 84.1 | 7 | 3.91 | 11.7 | 229.5 | 24.79 | 0.3913 |
Willow | 89.7 | 7 | 4.04 | 12.1 | 245 | 26.47 | 0.3665 |
Oak | 118.9 | 7 | 4.65 | 14 | 324.5 | 35.07 | 0.2767 |
Mulberry | 150.9 | 19 | 3.18 | 15.9 | 414.3 | 44.52 | 0.2192 |
Ash | 180.7 | 19 | 3.48 | 17.4 | 496.1 | 53.31 | 0.183 |
Elm | 211 | 19 | 3.76 | 18.8 | 579.2 | 62.24 | 0.1568 |
Poplar | 239.4 | 37 | 2.87 | 20.1 | 659.4 | 70.61 | 0.1387 |
Sycamore | 303.2 | 37 | 3.23 | 22.6 | 835.2 | 89.4 | 0.1095 |
Upas | 362.1 | 37 | 3.53 | 24.7 | 997.5 | 106.82 | 0.0917 |
Yew | 479 | 37 | 4.06 | 28.4 | 1319.6 | 141.31 | 0.0693 |
Totara | 498.1 | 37 | 4.14 | 29 | 1372.1 | 146.93 | 0.0666 |
Rubus | 586.9 | 61 | 3.5 | 31.5 | 1622 | 173.13 | 0.0567 |
Sorbus | 659.4 | 61 | 3.71 | 33.4 | 1822.5 | 194.53 | 0.0505 |
Araucaria | 821.1 | 61 | 4.14 | 37.3 | 2269.4 | 242.24 | 0.0406 |
Redwood | 996.2 | 61 | 4.56 | 41 | 2753.2 | 293.88 | 0.0334 |
ALUMINIUM ALLOY CONDUCTOR BS 3242 | |||||||
Code Name | Calculated Area | No. Of Wires | Diameter | Weight | Rated Strength | MAX .DC resistance at 20℃ | |
Wire | Cond. | ||||||
mm2 | mm | mm | kg/km | Kn | ohm/km | ||
Box | 15 | 7/1.85 | 18.82 | 5.55 | 51 | 537 | 1.7495 |
Acacia | 20 | 7/2.08 | 23.79 | 6.24 | 65 | 680 | 1.384 |
Almond | 25 | 7/2.34 | 30.1 | 7.02 | 82 | 861 | 1.0934 |
Cedar | 30 | 7/2.54 | 35.47 | 7.62 | 97 | 1014 | 0.9281 |
– | 35 | 7/2.77 | 42.18 | 8.31 | 115 | 1205 | 0.7804 |
Fir | 40 | 7/2.95 | 47.87 | 8.85 | 131 | 1367 | 0.688 |
Hazel | 50 | 7/3.30 | 59.87 | 9.9 | 164 | 1711 | 0.5498 |
Pine | 60 | 7/3.61 | 71.65 | 10.83 | 196 | 2048 | 0.4594 |
– | 70 | 7/3.91 | 84.05 | 11.73 | 230 | 2402 | 0.3917 |
Willow | 75 | 7/4.04 | 89.73 | 12.12 | 245 | 2565 | 0.3669 |
– | 80 | 7/4.19 | 96.52 | 12.57 | 264 | 2758 | 0.3441 |
– | 90 | 7/4.44 | 108 | 13.32 | 298 | 3112 | 0.3023 |
Oak | 100 | 7/4.65 | 118.9 | 13.95 | 325 | 3398 | 0.2769 |
– | 100 | 19/2.82 | 118.7 | 14.1 | 326 | 3393 | 0.2787 |
Mulbery | 125 | 19/3.18 | 150.9 | 15.9 | 415 | 4312 | 0.2192 |
Ash | 150 | 19/3.48 | 180.7 | 17.4 | 497 | 5164 | 0.1831 |
Elm | 175 | 19/3.76 | 211 | 18.8 | 580 | 6030 | 0.1568 |
Poplar | 200 | 37/2.87 | 239.4 | 20.09 | 659 | 8841 | 0.1385 |
– | 225 | 37/3.05 | 270.3 | 21.35 | 744 | 7724 | 0.1227 |
Sycamore | 250 | 37/3.22 | 303.2 | 22.54 | 835 | 8664 | 0.1093 |
Upas | 300 | 37/3.53 | 362.1 | 24.71 | 997 | 10350 | 0.09156 |
Walnut | 350 | 37/3.81 | 421.8 | 26.67 | 1162 | 12053 | 0.0786 |
Yew | 400 | 37/4.06 | 479 | 28.42 | 1319 | 13685 | 0.06921 |
Totara | 425 | 37/4.14 | 498.1 | 28.98 | 1372 | 14233 | 0.06656 |
Rubus | 500 | 61/3.50 | 586.9 | 31.5 | 1620 | 16771 | 0.05662 |
Araucaria | 700 | 61/4.14 | 821.1 | 37.26 | 2266 | 23450 | 0.04047 |
aluminum conductor |
Elative manufacturing standards: IEC83, IEC1089, 31, B232, BS215, DIN48204.
All Aluminum Conductor(AAC)& Aluminum Conductor Steel Reinforced(ACSR))for ASTM
(AAC, ACCR, AAAC, ACSR) Generally Confirming to IS 398 (Part-I, II, IV), IEC-228
(AAAC) Conductor as per ASTM-B-399-1992
(AAAC) Conductor as per BS-3242-1970
(AAAC) Conductor IS: 398-IV-1994
(ACSR) as per ASTM-B-233-1992 aluminum conductor
(AAC) as per BS-215-1-1970
(AAC) as per IS-398-1: 1976
(AAC) as per ASTM-B-231-1990
(ACSR) as per IS: 398-II: 1976 & IS: 398-V: 1992
(ACSR) BS-215-II-1970
(AACSR) as per IEC-1089-1191
AAC(All aluminum conductor) are suited for overhead power line. aluminum conductor
We can supply this conductor according to different recognized standards, such as IEC61089, BS215, BS EN 50182: 2001, ASTM B231, CSA C49, DIN480201, JIS C3109, customer special specification also can be satisfied.
Applications:
Used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.
aluminum conduc
Packaging & shipping
china cable supplier
Packaging Detail: export wooden drum pack bare acsr conductor, wooden iron drum and other export standard package
Delivery Detail: 10 days and also depend on the quantity
Q: Are you trading company or manufacturer ?
A: We are factory.
Q: How long is your delivery time?
A: Generally it is 5-10 days if the goods are in stock. or it is 15-20 days if the goods are not in stock, it is according to quantity.
Q: Do you provide samples ? is it free or extra ?
A: Yes, we could offer the sample for free charge but do not pay the cost of freight.
Q: What is your terms of payment ?
A: 30% T/T in advance,70% T/T balance before shipment
- Next: copper cable 1.5 mm 2.5mm 4mm 6mm 10mm house wiring Electrical cable copper single core PVC wire
- Previous: Best Quality 4 Core 35mm2 Copper Cable PVC Insulated Power Cable 95mm
Contact us