Power Cable 4 x 16mm2 4 x 10mm2 4 x 25mm2
0.6/1kV Low Voltage Cu/XLPE/PVC
product show :
| Power Cable 0.6/1kV Low Voltage Cu/XLPE/PVC | ||||||||||||
| No. | Description | Unit | Particulars | |||||||||
| 1 | Size | 4 x 10mm2 | 4 x 16mm2 | 4 x 25mm2 | ||||||||
| 2 | Applicable Standards | – | IEC 60502 | IEC 60502 | IEC 60502 | |||||||
| 3 | Rated Voltage | kV | 0.6/1kV | 0.6/1kV | 0.6/1kV | |||||||
| 4 | Conductor | |||||||||||
| 4.1 | Number of cores | No. | 4 | 4 | 4 | |||||||
| 4.2 | Material | – | Class 2 Stranded Plain Annealed Copper | |||||||||
| 4.3 | Nominal area | mm2 | 10 | 16 | 25 | |||||||
| 4.4 | Number and diameter of individual wire | No./mm | ||||||||||
| 4.5 | Max. DC resistance of conductor at 20℃ | Ω/km | #NAME? | #NAME? | #NAME? | |||||||
| 5 | Insulation | |||||||||||
| 5.1 | Material | – | XLPE | XLPE | XLPE | |||||||
| 5.2 | Nominal insulation thickness | mm | 0.7 | 0.7 | 0.9 | |||||||
| 5.3 | Minimum insulation thickness | mm | ||||||||||
| 5.4 | Core identification | A | Blue, Brown, Black and Grey | |||||||||
| B | Green/Yellow, Blue, Brown and Black | |||||||||||
| 6 | Outer sheath | |||||||||||
| 6.1 | Material | – | PVC | PVC | PVC | |||||||
| 6.2 | Nominal sheath thickness | mm | 1.8 | 1.8 | 1.8 | |||||||
| 6.3 | Minimum sheath thickness | mm | 1.43 | 1.43 | 1.43 | |||||||
| 6.4 | Color | Black | Black | Black | ||||||||
| 7 | Overall diameter of the cable | mm | 17.4 | 19.9 | 23.9 | |||||||
| 8 | Minimum Bending radius | mm | 208.8 | 238.8 | 286.8 | |||||||
| 9 | Cable Weight approx. | kg/km | 580 | 845 | 1260 | |||||||
| 10 | AC Test voltage (No breakdown) | kV/5min | 3.5 | 3.5 | 3.5 | |||||||
| 11 | Maximum allowable conductor temperature at full load and short circuit condition | ℃ | 90/250 | 90/250 | 90/250 | |||||||
| 1. Parameters can be changed according to your requirement such as color of insulation or others. | ||||||||||||
| 2. Parameters may be a little different due to other factors in the process of production. | ||||||||||||