Overhead bare conductor acsr dog conductor price list

Place of Origin: | Henan China |
Brand Name: | SANHE CABLE |
Model Number: | Dog |
Insulation Material: | None |
Type: | High Voltage |
Application: | Overhead |
Conductor Material: | Aluminum |
Jacket: | None |
Selling Units: | Single item |
Single package size: | 100X10X10 cm |
Single gross weight: | 0.87 KG |
1.Application
Used as bare overhead transmission conductor and as primary and secondary distribution conductor and messenger support. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.
2 .Service Performance
(1).The permissible long-time operating temperature for aerial conductor is 70oC.
(2).Under the circumstance that rare climate is occuring and ice coverage rate low in heavy ice area,the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.
(3).When connecting conductors,the conductor beside the connecting tube cant be prominent.Otherwise,the force on the operating conductors will be unbalanced.After connectors are install,the connecting tube should be painted by moisture-proof varnish in order to protect it from corrosion.
(4).Under installaion,the arc downing stress of all the conductors should be the same.With in the permissible distance of crossing buildings or dropping to the ground,the stress can be 10-15% higher than regular stress.
3.Product Performance
(1).The electrical performance of AAC and ACSR is indicated in DCΩ/km(20oC).The resistivity of the hard aluminum wire for stranded wires is not greater than 28.264 nΩ. m of international standard value.
(2).The rated tensile strength of AAC is denoted with the result of total cross-section of all aluminum conductors multiplied by min.tensile of corresponding size specified in the standard for aluminum wire.
(3).The rated tensile strengh of ACSR is denoted with sum of all aluminum conductorstensile strength and steels tensile strength.
a.The tensile strength of all aluminum conductors is denoted with the result of all cross-sections of aluminum conductors multiplied by min.tensile strength of corresponding size specified in the standard for aluminum wire.
b.The tensile strength of all steel wire is denoted with the result of all cross-sections of steel wires multiplied by the stress at 1% elongation of corresponding size specified in the standard for steel wire.
Code Name |
Nominal Area |
Stranding &Wire Dia. |
Approximate Overall Dia. |
Approximate Weight |
Breaking Load |
DC Resistance at 20℃ |
Current Rating |
|
Aluminum |
Steel |
|
|
|
|
|
||
mm2
|
No. |
No. |
mm
|
Kg/km |
kN |
Ω/km |
A |
|
Ferret |
40 |
6 |
1 |
9 |
171.7 |
15.20 |
0.6766 |
161 |
Rabbit |
50 |
6 |
1 |
10.05 |
214.1 |
18.35 |
0.5426 |
185 |
Dog |
100 |
6 |
7 |
14.15 |
394.7 |
32.70 |
0.2733 |
278 |
Wolf |
150 |
30 |
7 |
18.13 |
725.9 |
69.20 |
0.1828 |
355 |
Dingo |
150 |
18 |
1 |
16.75 |
507.4 |
35.70 |
0.1815 |
349 |
Lynx |
175 |
30 |
7 |
19.53 |
842.4 |
79.80 |
0.1576 |
386 |