N2XS2Y Cable, YJY Cable

Port: | Shanghai Port |
Payment Terms: | L/C,T/T |
Supply Ability: | 3000000 Meter/Meters per Month |
Place of Origin: | Shanghai China |
Brand Name: | Xinxin |
Model Number: | N2XS2Y/YJY Power Cable |
Insulation Material: | XLPE |
Type: | Medium Voltage |
Application: | Underground |
Conductor Material: | Copper |
Jacket: | PVC |
Delivery Detail: | according to ur order quantity |
Packaging Detail: | XLPE Power cable Wooden Drum. |
Copper core, XLPE insulated, PE sheath
N2XS2Y CABLE
Cable structure
- Circular bare copper core, stranded according to HD 383, IEC 60228
- Inner semi-conducting coating
- Core insulation of cross-linked polyethylene (XLPE)
- Insulation thickness: 6/10 kV = 3,4 mm; 12/20 kV = 5,5 mm; 18/30 kV = 8,0 mm
- Outer semi-conducting coating spliced with the insulation
- Tape of conductive material
- Screening of copper wires and one or two copper tapes contrary applied
- Wrapping with non-conducting tape
- Sheath of PE compound, color black, sheath thickness 2,5 mm
Technical data
- XLPE-insulated cable according to DIN VDE 0276 part 620, HD 620 and IEC 60502
- Temperature range max. +90 °C during installation from -5 °C to +70 °C Short circuit temperature 250 °C (up to 5 seconds)
- Nominal voltages Uo/U 6/10 kV, 12/20 kV, 18/30 kV
- Operating voltages for 6/10 kV = max. 12 kV; 12/20 kV = max. 24 kV; 18/30 kV = max. 36 kV
- Test voltage a.c. for 6/10 kV = 21 kV up to 5 min. 12/20 kV = 42 kV up to 5 min. 18/30 kV = 63 kV up to 5 min.
- Minimum bending radius approx. 15 x cable diameter
Application
Cable suitable for installation in cable ducts, power plants as well as for outer laying into earth, water or for installation in distribution boards. Due to its good shaping characteristics, this cable can also be laid even in difficult line guideways. To avoid the influence of the outer interferences, an adherent semiconductive layer is extruded between the conductor and the insulation. We recommend the use of stripping tool for correct installation.
N2XS2Y 6/10 kV
Ordering code | Number of cores | × | core cross section [mm2] | Approx. outer ø min.[mm] | Approx. outer ø max.[mm] | Cooper weight [kg/km] | Approx. cable weight [kg/km] | |
---|---|---|---|---|---|---|---|---|
0932480 | 1 | × | 35 | rm/16 | 23 | 28 | 518 | 900 |
0932481 | 1 | × | 50 | rm/16 | 24 | 29 | 662 | 950 |
0932482 | 1 | × | 70 | rm/16 | 26 | 31 | 860 | 1200 |
0932483 | 1 | × | 95 | rm/16 | 27 | 32 | 1098 | 1450 |
0932484 | 1 | × | 120 | rm/16 | 29 | 34 | 1340 | 1700 |
0932485 | 1 | × | 150 | rm/16* | 30 | 35 | 1622 | 1950 |
0932486 | 1 | × | 150 | rm/25 | 30 | 35 | 1725 | 2050 |
0932487 | 1 | × | 185 | rm/16* | 32 | 37 | 1958 | 2350 |
0932488 | 1 | × | 185 | rm/25 | 32 | 37 | 2059 | 2400 |
0932489 | 1 | × | 240 | rm/16* | 34 | 39 | 2486 | 2900 |
0932490 | 1 | × | 240 | rm/25 | 34 | 39 | 2587 | 2950 |
0932491 | 1 | × | 300 | rm/25 | 36 | 41 | 3163 | 3550 |
0932492 | 1 | × | 400 | rm/35 | 40 | 45 | 4234 | 4500 |
0932493 | 1 | × | 500 | rm/35 | 43 | 48 | 5194 | 5500 |
N2XS2Y 12/20 kV
Ordering code | Number of cores | × | core cross section [mm2] | Approx. outer ø min.[mm] | Approx. outer ø max.[mm] | Cooper weight [kg/km] | Approx. cable weight [kg/km] | |
---|---|---|---|---|---|---|---|---|
0932494 | 1 | × | 35 | rm/16 | 27 | 32 | 518 | 1150 |
0932495 | 1 | × | 50 | rm/16 | 28 | 33 | 662 | 1300 |
0932496 | 1 | × | 70 | rm/16 | 30 | 35 | 854 | 1350 |
0932497 | 1 | × | 95 | rm/16 | 31 | 36 | 1094 | 1650 |
0932498 | 1 | × | 120 | rm/16 | 33 | 38 | 1334 | 1900 |
0932499 | 1 | × | 150 | rm/16* | 54 | 39 | 1622 | 2150 |
0932500 | 1 | × | 150 | rm/25 | 34 | 39 | 1723 | 2250 |
0932501 | 1 | × | 185 | rm/16* | 36 | 41 | 1958 | 2550 |
0932502 | 1 | × | 185 | rm/25 | 36 | 41 | 2059 | 2600 |
0932503 | 1 | × | 240 | rm/16* | 39 | 44 | 2486 | 3100 |
0932504 | 1 | × | 240 | rm/25 | 39 | 44 | 2587 | 3200 |
0932505 | 1 | × | 300 | rm/25 | 41 | 46 | 3163 | 3800 |
0932506 | 1 | × | 400 | rm/35 | 44 | 49 | 4234 | 4750 |
0932507 | 1 | × | 500 | rm/35 | 47 | 52 | 5194 | 5800 |
N2XS2Y 18/30 kV
Ordering code | Number of cores | × | core cross section [mm2] | Approx. outer ø min.[mm] | Approx. outer ø max.[mm] | Cooper weight [kg/km] | Approx. cable weight [kg/km] | |
---|---|---|---|---|---|---|---|---|
0932508 | 1 | × | 50 | rm/16 | 33 | 38 | 662 | 1350 |
0932509 | 1 | × | 70 | rm/16 | 35 | 40 | 854 | 1600 |
0932510 | 1 | × | 95 | rm/16 | 36 | 41 | 1094 | 1900 |
0932511 | 1 | × | 120 | rm/16 | 38 | 43 | 1334 | 2150 |
0932512 | 1 | × | 150 | rm/25 | 39 | 44 | 1723 | 2550 |
0932513 | 1 | × | 185 | rm/25 | 41 | 46 | 2059 | 2900 |
0932514 | 1 | × | 240 | rm/25 | 43 | 48 | 2587 | 3500 |
0932515 | 1 | × | 300 | rm/25 | 46 | 51 | 3163 | 4150 |
0932516 | 1 | × | 400 | rm/35 | 49 | 54 | 4234 | 5100 |
0932517 | 1 | × | 500 | rm/35 | 52 | 57 | 5194 | 6200 |