IV 300V PVC Insulated Single Core Building Wire

IV 300V PVC Insulated Single Core Building Wire
Port: Qingdao
Payment Terms: L/C,T/T
Supply Ability: 2000 Kilometer/Kilometers per Week
Place of Origin: Henan China
Brand Name: Yifang
Model Number: IV
Type: Insulated
Application: building wire
Conductor Material: Copper
Conductor Type: solid or stranded
Insulation Material: PVC
Standard: IEC
Certification: CCC/CE/ISO9001
Conductor: Solid or stranded annealed copper, size 0.5mm2 to 150mm2
Voltage: 300V 450V 500V 750V
Color: Green Red Yellow Black Green or as required
Delivery Detail: Shipped in 20 days after payment
Packaging Detail: Packing as requirement
Our Company

Zhengzhou Yifang Cable Co.,Ltd.http://yifang.en.alibaba.com is mainly specialized in Wires and Cables, including designment, production and sales.

The products are complying with GB,IEC,BS,ASTM,ect. Besides,we have the capacity to desigh and produce all kinds of wires and cables according to your special requirments.
In the past years, our products have been sold to many countries and regions, such as Australia, Algeria, Bolivia, Brazil, Chile,Iran, Malaysia,Mexico, Russia, Tanzania, Zambia,etc.

Parts of certifications and our clients from all around the world.

Product Description

Range of Application

The PVC insulated building wire belongs to the series of laying wires, which are mainly suitable for laying at the fixed places.They are widely used as connectors of driving, lighting, electric equipments,instrument and telecommunication equipments with rated voltage up to 450/750V. Part of the plastic wire are used at the equipment with AC rated voltage up to 300/300V.

Standard

The products adopt the standard GB5023.1-7-1997《PVC insulated wire with rated voltage up to 450/750V 》, ib8734.1-5-1998《PVCinsulated cable,wire and flexible wire with rated voltage up to 450/750V》and Q/ZEL02-2002《Plastic insulatedwire and cable》. Among them,GB5023.1-7-1997is identical with IEC227,and the types are the same as the stipulation of the IEC,technical specification is just the same ,and more we have extended the range of the types to be fit for the requirement of the consumers.JB8374.1-5-1998 and Q/ZEL02-2002 are the complementary content of the standard GB5023.1-7-1997,and the standard Q/ZEL02-2002 is replenished to meet the requirement of consumers.

227 IEC 05 IV 300/500V

Nominal Area mm2
No. /Wire Dia. mm
Nominal thickness of insulation mm
Max. overall Dia. mm
Resistance at 20℃ Ohm/Km
Min. insulation resistance at 70℃ Mohm/Km
Total weight Kg/Km
0.5
1/0.8
0.6
2.4
36
0.015
8.1
0.75
1/0.97
0.6
2.6
24.5
0.012
10.6
0.75
7/0.37
0.6
2.8
24.5
0.012
12.0
1
1/1.13
0.6
2.8
18.1
0.011
13.2
1
7/0.43
0.6
3.0
18.1
0.011
15.0

227 IEC 01 IV 450/750V

Nominal Area mm2
No. /Wire Dia. mm
Nominal thickness of insulation mm
Max. overall Dia. mm
Resistance at 20℃ Ohm/Km
Min. insulation resistance at 70℃ Mohm/Km
Total weight Kg/Km
Cu
Al
Cu
Al
1.5
7/0.52
0.7
3.5
12.1
*
0.01
20.6
*
2.5
7/0.68
0.8
4.2
7.41
11.8
0.01
34.8
17
4
7/0.85
0.8
4.4
4.61
7.39
0.0085
47.1
22
6
7/1.04
0.8
5.4
3.08
4.91
0.007
71.2
29
10
7/1.35
1.0
7.0
1.83
3.08
0.0065
110
52
16
7/1.70
1.0
8.0
1.15
1.91
0.005
170
70
25
7/2.14
1.2
10.0
0.727
1.2
0.005
270
110
35
7/2.52
1.2
11.5
0.524
0.868
0.004
364
150
50
19/1.78
1.4
13.0
0.387
0.641
0.0045
500
200
70
19/2.14
1.4
15.0
0.268
0.443
0.0035
688
269
95
19/2.52
1.6
17.5
0.193
0.32
0.0035
953
360
120
37/2.03
1.6
19.0
0.153
0.253
0.0032
1168
449
150
37/2.25
1.8
21.0
0.124
0.206
0.0032
1466
551
185
37/2.52
2.0
32.5
0.099
0.164
0.0032
1808
668

Detailed Image