five cores flexible wire flexible conductor insulated wire

five cores flexible wire flexible conductor insulated wire
Port: Qingdao
Payment Terms: L/C,T/T,Western Union,MoneyGram
Supply Ability: 50 Kilometer/Kilometers per Day ensure five cores flexible wire order
Place of Origin: Henan China
Brand Name: Hongda
Model Number: RVV
Type: Insulated
Application: building
Conductor Material: Copper
Conductor Type: Stranded
Insulation Material: PVC
standard: BS-6500 & IEC-60227-5
colour: blue black yellow green red
main export country: usa india austrilia phillippenes pakistan indonesia
HS: 8544492100
core: 5
Packaging Detail: in coil or as your order

  we are a professional manufacturer of     types of     five cores flexible wire    ,We have the best R&D, production, sales and service team and modern enterprise management organization.

 Applications

  This cable may prevent human from being suffocated by toxic gas generated from accidental burning of cable. They are suitable for use in the circumstance demanding strict fire-resistance and environmental-protecting, such as high-rise building, hospitals, subways and shopping malls etc.

STANDARD

 ISO IEC CCC

Using features

  1. This product fit for AC voltage 450/750V and below of domestic electrical appliances. Of smaller size motoriace tools, of instruments, of various meters and motorized lighting installations. 
2. Electric wire has high quality and low price. We can also produce products according to your special requirement. 
3. We promise you of the most competitive prices. If you need, we can offer you some samples for your reference. 
4. Range of application: Fit A. C rated voltage 450/750V. 
5. Rated temperature of the wire is 70 centigrade. 
6. Finished insualtion core and finished power line are put into the water at the temperature 20+50° For an hour, they should be able to bear stipulated acsohz, soaked voltagetest at stated. 
7. Wire has excellent electric insulation property. Mechnical property, non-inflammability, so it is safe and convent in using

Type

 

 

Dimensions – conductor cross-section Construction of individual conductor External diameter Insulation thickness  Conductor resistance at 20 °C Specific. el. resistance of insulation at 70°C Cable weight
  nominal min-max. nominal max min. approx.
mm² n x mm mm mm Ω/km MΩkm kg/km
1,5 30 x 0,25 2,8 – 03,4 0,7 13,3 0,0100 20
2,5 50 x 0,25 3,4 – 04,1 0,8 7,98 0,0095 32
4 56 x 0,30 3,9 – 04,8 0,8 4,95 0,0078 46
6 84 x 0,30 4,4 – 05,3 0,8 3,30 0,0068 65
10 80 x 0,40 5,7 – 06,8 1,0 1,91 0,0065 115
16 128 x 0,40 6,7 – 08,1 1,0 1,21 0,0053 170
25 200 x 0,40 8,4 – 10,2 1,2 0,780 0,0050 260
35 280 x 0,40 9,7 – 11,7 1,2 0,554 0,0043 360
50 400 x 0,40 11,5 – 13,9 1,4 0,386 0,0042 515
70 356 x 0,50 13,2 – 16,0 1,4 0,272 0,0036 710
95 485 x 0,50 15,1 – 18,2 1,6 0,206 0,0036 940

 

 