Factory price With XLPE Insulation PE Jacket 35 KV~500kv High Voltage Power Cable Single Core 630mm2

Port: | Qingdao/Tianjin/Shanghai |
Payment Terms: | L/C,T/T |
Supply Ability: | 28000 Meter/Meters per Week |
Place of Origin: | Henan China |
Brand Name: | ZMS Cable/OEM |
Model Number: | PVC Sheath Power Cable |
Insulation Material: | PVC/XLPE/PE |
Type: | High Voltage |
Application: | Construction |
Conductor Material: | Aluminum |
Jacket: | PVC |
Rated Voltage: | 11kv |
Dimensions: | 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70,95, 120, 150, 185, 240, 300,400 |
No. of Cores: | 1C, 2C, 3C, 3C+1C, 3C+2C, 4C, 4C+1C, 5C |
Conductor: | Stranded round compacted copper or aluminum conductor (Cu/Al) |
Insulation: | PVC,XLPE,PE |
Armoring Type: | SWA, AWA, STA, DSTA, GSWA |
Sheath: | PVC (Polyvinyl Chloride) |
Color: | Black or Red as per requirements |
Operating Temperature: | 0°C to 90°C(70℃ for PVC insulation) |
Standards: | IEC60502-1, BS6346, BS5467, BS6360, BS6724, VDE0276, etc. |
Packaging Detail: | PVC Sheathed Power Cable in coils, reels or on standard cable drums |
Product Description
XLPE power cable is used to transmit and distribute power in power transmission and distribution system of 35kV~500kV.
It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication
in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable.
TYPE & DESIGNATION OF BARE CONDUCTOR
127/220(245)KV
Nominal Cross Section Area | Capacitance | Inductance | Current Rating |
---|---|---|---|
mm² | μF/mm | mH/km | A |
500 | 0.14 | 1.42 | 5.8 |
630 | 0.16 | 1.4 | 6.4 |
800 | 0.17 | 1.37 | 6.9 |
1000 | 0.19 | 1.35 | 7.4 |
1200 | 0.2 | 1.33 | 7.8 |
1400 | 0.21 | 1.32 | 8.2 |
1600 | 0.22 | 1.31 | 8.6 |
230/400(420)KV
Nominal Cross Section Area | Capacitance | Inductance | Current Rating |
---|---|---|---|
mm² | μF/mm | mH/km | A |
630 | 0.13 | 1.4 | 9.6 |
800 | 0.15 | 1.37 | 10.7 |
1000 | 0.16 | 1.35 | 11.7 |
1200 | 0.18 | 1.33 | 12.9 |
1400 | 0.19 | 1.32 | 13.5 |
1600 | 0.19 | 1.31 | 14.1 |
Technical Data
127/220(245)KV
Nominal Cross Section Area | Nominal Conductor Diameter | Nominal Insulation Thickness | Nominal Diameter Over Insulation | Nomanal Lead Sheath Thickness | Nominal Overall Diameter | Weight |
---|---|---|---|---|---|---|
mm² | mm | mm | mm | mm | mm | kg/m |
500 | 26.2 | 24 | 77.6 | 2.9 | 111 | 29.3 |
630 | 29.8 | 23 | 79.2 | 3 | 112.8 | 31.2 |
800 | 33.7 | 23 | 83.1 | 3.1 | 117.5 | 34.5 |
1000 | 37.9 | 23 | 87.3 | 3.1 | 121.9 | 37.7 |
1200 | 41.2 | 23 | 90.6 | 3.1 | 125.2 | 40.4 |
1400 | 44.4 | 23 | 93.8 | 3.1 | 128.6 | 43.2 |
1600 | 47.4 | 23 | 96.8 | 3.1 | 131.8 | 46 |
230/400(420)KV
Nominal Cross Section Area | Nominal Conductor Diameter | Nominal Insulation Thickness | Nominal Diameter Over Insulation | Nomanal Lead Sheath Thickness | Nominal Overall Diameter | Weight |
---|---|---|---|---|---|---|
mm² | mm | mm | mm | mm | mm | kg/m |
630 | 29.8 | 32 | 98.2 | 3.1 | 132.8 | 38.8 |
800 | 33.7 | 30 | 98.1 | 3.1 | 133.1 | 40.2 |
1000 | 37.9 | 29 | 100.3 | 3.1 | 135.3 | 42.6 |
1200 | 41.2 | 27 | 99.6 | 3.1 | 134.6 | 44 |
1400 | 44.4 | 27 | 102.8 | 3.1 | 138 | 46.9 |
1600 | 47.4 | 27 | 105.8 | 3.1 | 141 | 49.7 |
Detailed Images
Packaging & Shipping
Certifications
- Next: China ASTM ACSR Conductor ACSR Cable ZMS Cable
- Previous: Bare Conductor Aluminum Cable Overhead Transmission Line 95mm2
Contact us
Search
You May Like
- No related articles