Our company is a professional manufacturer of cu/xlpe/pvc/swa/pvc armoured power cables .We have the best R&D, production, sales and service team and modern enterprise management organization
Application:
Suitable for use in power distribution lines or fixed installation
Operating Characteristics:
*Max.short-circuit temperature of conductor shall not exceed(5s maximum duration):
Cross-section of conductor ≤300mm2 160°C;
Cross-section of conductor > 300mm2 140 °C .
*The ambient temperature under installation of cable should not below 0 °C .
*The bending radius of cable should not less than 10 times of diameter of the cable.
(1).The long-time permissible operation temperature of conductor shall not be higher than 70°C.
(2).Conductor maximum short circuit(not more than 5 seconds)temperature shall not be higher than 160 °C .
(3).The power cable is not limited by drop in level when being laid, and the ambient temperature shall not be lower than 0 °C .
(4).Perfect chemical stability,resistant against acids,alkalis,grease and organic solvents, and flame.
(5).Light weight,perfect bending properties,installed and maintained easily and conveniently.
We provide armoured type and non-armored type for the power cables above.
Operating conditon when cable laying
in Air
1.The single-core cables are paralled laid,the distance between the cable center is 2 times diameter of the csble for cross section of conductor ≤ 185mm2 and 90mm for cross section of conductor ≥240mm2.
2.Ambient air temperature:40 °C
3.Max.permissible continuous opesating temperature of conductor:70 °C
Direct in ground
1.When the single-core cables are installed seperately,the distance between the cables center is 2 times diameter of the cable
2.Solid temperature :25°C
3.Max.permissible continuous operating temperature of conductor:70 °C
4.Solid thermal resistivity:10 °Cm/w
5.Depth of laying:0.7m
| ABC cable | electrical wire | power cable |
| armored power cable | Concentric cable | control cable |