BS 5467 SWA Armoured Power Cables, 600/1000V

BS 5467 SWA Armoured Power Cables, 600/1000V
Port: Qingdao or Shanghai
Payment Terms: L/C,D/A,D/P,T/T,Western Union,MoneyGram
Supply Ability: 1500 Kilometer/Kilometers per Month
Place of Origin: Henan China
Brand Name: Hongda
Model Number: YJV32
Insulation Material: XLPE
Type: Low Voltage
Application: Underground
Conductor Material: Copper
Jacket: PVC
Product name: BS 5467 SWA Armoured Power Cables, 600/1000V
Conductor: Pure Copper
Core: 4 Core
Insulation: XLPE PVC
Sheath: Flame Retardant PVC
Standard: BS IEC ASTM DIN
Certificate: ISO9001 CCC
Rated voltage: 600/1000 Volts
Delivery Detail: Shipped in 15 days after payment
Packaging Detail: wooden or iron drum

BS 5467 SWA Armoured Power Cables, 600/1000V

Product Description
 Applications

These cables are used for power and control circuits, they can offer excellent protection through the use of a heavy galvanized steel wire armour. The GSWA makes them suitable for use inside and outside buildings or for direct burial in the ground.

Construction

Conductor Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460, IEC 60228.
Insulation XLPE (Cross-Linked Polyethylene) Type GP 8 or ethylene propylene rubber (GP 6)
Colour Code 1 Core : Brown
  2 Cores: Brown or Blue
  3 Cores: Brown, Black, Grey
  4 Cores: Blue, Brown, Black, Grey
  5 Cores: Green/Yellow, Blue, Brown, Black, Grey
  Above 5 Cores: White Cores with black numbers
Bedding PVC (Polyvinyl Chloride)
Armour Single Core: AWA (Aluminum Wire Armour)
  Multi Core: SWA (Steel Wire Armour)
Outer Sheath PVC(Polyvinyl Chloride)

Technical Information

Voltage rating 600/1000V
Temperature rating 0°C to +90°C
Bending radius 1.5mm² to 16mm² : 6 x overall diameter
  25mm² and above : 8 x overall diameter
Flame retardant IEC60332 part 1, BS4066 part 1

Cable Parameter

Single-core 600/1000V cables 

1
Nominal Cross-sectional Area Strand Type Nominal Insulation thickness Nominal Bedding thickness Nominal Alum Wire dia. Nominal Sheath thickness Approx. Overall Diameter Aprrox Weight
mm² No./mm mm mm mm mm mm kg/km
1×50 19/1.78 1.0 0.8 0.9 1.5 17.5 800
1×70 19/2.14 1.1 0.8 1.25 1.5 20.2 990
1×95 19/2.52 1.1 0.8 1.25 1.6 22.3 1280
1×120 37/2.03 1.2 0.8 1.25 1.6 24.2 1550
1×150 37/2.25 1.4 1 1.6 1.7 27.4 1900
1×185 37/2.52 1.6 1 1.6 1.8 30.0 2320
1×240 61/2.25 1.7 1 1.6 1.8 32.8 2930
1×300 61/2.52 1.8 1 1.6 1.9 35.6 3580
1×400 61/2.85 2.0 1.2 2.0 2.0 40.5 4600
1×500 61/3.20 2.2 1.2 2.0 2.1 44.2 5680
1×630 127/2.52 2.4 1.2 2.0 2.2 48.8 7160
1×800 127/2.85 2.6 1.4 2.5 2.4 55.4 9315
1×1000 127/3.20 2.8 1.4 2.5 2.5 60.6 11490

Two-core 600/1000V cables 

Nominal Cross-sectional Area Strand Type Nominal Insulation thick-ness Nominal Bedding thickness Nominal Steel Wire Armor dia. Nominal Sheath thickness Approx. Overall Diameter Aprrox Weight
Extruded bedding Taped bedding
mm^2 No./mm mm mm mm mm mm mm kg/km
2×1.5 7/0.53 0.6 0.8 0.9 1.4 12.1 320
2×2.5 7/0.67 0.7 0.8 0.9 1.4 13.6 365
2×4 7/0.85 0.7 0.8 0.9 1.4 14.7 440
2×6 7/1.04 0.7 0.8 0.9 1.4 15.9 470
2×10 7/1.35 0.7 0.8 0.9 1.5 18.0 800
2×16 7/1.70 0.7 0.8 1.25 1.5 20.4 20.4 900
2×25 7/2.14 0.9 0.8 1.25 1.6 24.1 24.1 1240
2×25* 7/2.14 0.9 0.8 1.25 1.6 20.4 20.4 1240
2×35 7/2.52 0.9 1 1.6 1.7 27.7 27.3 1710
2×35* 7/2.52 0.9 1 1.6 1.7 23.3 22.9 1710
2×50* 19/1.78 1.0 1 1.6 1.8 25.8 25.4 1800
2×70* 19/2.14 1.1 1 1.6 1.9 29.0 28.6 2320
2×95* 19/2.52 1.1 1.2 2.0 2.0 33.1 32.3 3150
2×120* 37/2.03 1.2 1.2 2.0 2.1 36.1 35.3 3880
2×150* 37/2.25 1.4 1.2 2.0 2.2 39.3 38.5 4820
2×185* 37/2.52 1.6 1.4 2.5 2.4 44.7 43.5 5920
2×240* 61/2.25 1.7 1.4 2.5 2.5 49.0 47.8 7300
2×300* 61/2.52 1.8 1.6 2.5 2.6 53.5 51.9 8770
2×400* 61/2.85 2 1.6 2.5 2.8 59.0 57.4 10905

* D-Shaped stranded conductor (class 2)

 

Three-core 600/1000V cables 

Nominal Cross-sectional Area Strand Type Nominal Insulation thickness Nominal Bedding thickness Nominal Steel Wire Armor dia. Nominal Sheath thickness Approx. Overall Diameter Aprrox Weight
Extruded bedding Taped bedding
mm^2 No./mm mm mm mm mm mm mm kg/km
3×1.5 7/0.53 0.6 0.8 0.9 1.3 12.6 340
3×2.5 7/0.67 0.7 0.8 0.9 1.4 14.1 408
3×4 7/0.85 0.7 0.8 0.9 1.4 15.3 498
3×6 7/1.04 0.7 0.8 0.9 1.4 16.6 600
3×10 7/1.35 0.7 0.8 1.25 1.5 19.5 915
3×16 7/1.70 0.7 0.8 1.25 1.6 21.6 21.6 1130
3×25 7/2.14 0.9 1 1.6 1.7 26.7 26.3 1710
3×25* 7/2.14 0.9 1 1.6 1.7 23.6 23.2 1710
3×35 7/2.52 0.9 1 1.6 1.8 29.4 29.0 2100
3×35* 7/2.52 0.9 1 1.6 1.8 25.7 25.3 2100
3×50* 19/1.78 1.0 1 1.6 1.8 28.5 28.1 2450
3×70* 19/2.14 1.1 1 1.6 1.9 32.2 31.8 3120
3×95* 19/2.52 1.1 1.2 2.0 2.1 37.0 36.2 4310
3×120* 37/2.03 1.2 1.2 2.0 2.2 40.4 39.6 5160
3×150* 37/2.25 1.4 1.4 2.5 2.3 45.5 44.3 7160
3×185* 37/2.52 1.6 1.4 2.5 2.4 49.8 48.6 8600
3×240* 61/2.25 1.7 1.4 2.5 2.6 55.1 53.9 10755
3×300* 61/2.52 1.8 1.6 2.5 2.7 60.2 58.6 13080
3×400* 61/2.85 2 1.6 2.5 2.9 66.6 65.0 15810

*Shaped stranded conductor (class 2)

 

Four-core 600/1000V cables 

Nominal Cross-sectional Area Strand Type Nominal Insulation thickness Nominal Bedding thickness Nominal Steel Wire Armor dia. Nominal Sheath thickness Approx. Overall Diameter Aprrox Weight
Extruded bedding Taped bedding
mm^2 No./mm mm mm mm mm mm mm kg/km
4×1.5 7/0.53 0.7 0.8 0.9 1.4 13.3 390
4×2.5 7/0.67 0.7 0.8 0.9 1.4 15.0 470
4×4 7/0.85 0.7 0.8 0.9 1.4 16.4 580
4×6 7/1.04 0.7 0.8 1.25 1.5 18.7 805
4×10 7/1.35 0.7 0.8 1.25 1.5 21.1 1090
4×16 7/1.70 0.7 0.8 1.25 1.6 23.4 23.4 1320
4×25 7/2.14 0.9 1 1.6 1.7 28.9 28.5 1840
4×25* 7/2.14 0.9 1 1.6 1.7 26.1 25.7 1840
4×35 7/2.52 0.9 1 1.6 1.8 31.9 31.5 2310
4×35* 7/2.52 0.9 1 1.6 1.8 28.6 28.2 2310
4×50* 19/1.78 1.0 1 1.6 1.9 32.0 31.6 2970
4×70* 19/2.14 1.1 1.2 2.0 2.1 37.7 36.9 4240
4×95* 19/2.52 1.1 1.2 2.0 2.2 41.7 40.9 5400
4×120* 37/2.03 1.2 1.4 2.5 2.3 47.1 45.9 7000
4×150* 37/2.25 1.4 1.4 2.5 2.4 51.4 50.2 8350
4×185* 37/2.52 1.6 1.4 2.5 2.6 56.6 55.4 10130
4×240* 61/2.25 1.7 1.6 2.5 2.7 63.0 61.4 12840
4×300* 61/2.52 1.8 1.6 2.5 2.9 68.8 67.2 15530
4×400* 61/2.85 2 1.8 3.15 3.2 78.1 76.1 19950

* Shaped stranded conductor (class 2)

 

Five-core 600/1000 V cables 

Nominal Cross-sectional Area Strand Type Nominal Insulation thickness Nominal Bedding thickness Nominal Steel Wire Armor dia. Nominal Sheath thickness Approx. Overall Diameter Aprrox Weight
Extruded bedding Taped bedding
mm^2 No./mm mm mm mm mm mm mm kg/km
5×1.5 7/0.53 0.6 0.8 0.9 1.4 14.3 430
5×2.5 7/0.67 0.7 0.8 0.9 1.4 16.1 545
5×4 7/0.85 0.7 0.8 0.9 1.5 17.8 680
5×6 7/1.04 0.7 0.8 1.25 1.5 20 840
5×10 7/1.35 0.7 0.8 1.25 1.6 22.9 1105
5×16 7/1.70 0.7 1 1.6 1.7 26.6 26.2 1450
5×25 7/2.14 0.9 1 1.6 1.8 31.5 31.1 2245
5×35 7/2.52 0.9 1 1.6 1.9 34.8 34.4 2840
5×50 19/1.78 1.0 1.2 2 2 40.4 39.6 3895
5×70 19/2.14 1.1 1.2 2 2.2 46.3 45.5 5145

Multi-core 600/1000 V cables with stranded copper conductors

Nominal Cross-sectional Area Strand Type Nominal Insulation thickness Nominal Bedding thickness Nominal Steel Wire Armor dia. Nominal Sheath thickness Approx. Overall Diameter Aprrox Weight
mm^2 No./mm mm mm mm mm mm kg/km
7×1.5 7/0.53 0.6 0.8 0.9 1.4 15.2 500
12×1.5 7/0.53 0.6 0.8 1.25 1.5 19.4 820
19×1.5 7/0.53 0.6 0.8 1.25 1.6 22.2 1080
27×1.5 7/0.53 0.6 1 1.6 1.7 26.7 1550
37×1.5 7/0.53 0.6 1 1.6 1.7 29 1850
48×1.5 7/0.53 0.6 1 1.6 1.8 32.7 2250
7×2.5 7/0.67 0.7 0.8 0.9 1.4 17.1 730
12×2.5 7/0.67 0.7 0.8 1.25 1.6 22.4 1020
19×2.5 7/0.67 0.7 1 1.6 1.7 26.6 1530
27×2.5 7/0.67 0.7 1 1.6 1.8 30.7 1960
37×2.5 7/0.67 0.7 1 1.6 1.8 33.8 2450
48×2.5 7/0.67 0.7 1.2 2 2 39.3 3260
7×4 7/0.85 0.7 0.8 1.25 1.5 19.7 840
12×4 7/0.85 0.7 1 1.6 1.6 25.7 1390
19×4 7/0.85 0.7 1 1.6 1.7 29.3 1850
27×4 7/0.85 0.7 1 1.6 1.9 34.4 2350
37×4 7/0.85 0.7 1.2 2 2 39.2 2800
48×4 7/0.85 0.7 1.2 2 2.1 44.1 3250

 

 
Company Information

  

Packaging & Shipping

 

Why Choose Us

 

1. We have a large production base, and advanced production equipment
2. Have an competitive price and high quality
3. Excellent after-sale service
4. Free issue:packaging list,invoice
5. Powerful technology team
6. Strict quality assurance system and perfect testing means
7. Advanced process equipment
8. Delivery on time
9. Our cable sales to Middle East,Africa,Russia,Southeast Asia, etc.
10.We have a good reputation in the overseas

 

 

 

 

FAQ

 

Q: Are you trading company or manufacturer ?

A: We are factory.

Q: How long is your delivery time?

A: Generally it is 5-10 days if the goods are in stock. or it is 15-20 days if the goods are not in stock, it is according to quantity.

Q: Do you provide samples ? is it free or extra ?

A: Yes, we could offer the sample for free charge but do not pay the cost of freight.

Q: What is your terms of payment ?

A: 30% T/T in advance,70% T/T balance before shipment

If you have another question, pls feel free to contact us as below

Contact us

 Tina Sales Director

 

 

 

Tags: ,

Contact us

 

 

 

Search