Best seller single pvc insulated wire with CE Certificate

Best seller single pvc insulated wire with CE Certificate
Port: Qingdao
Payment Terms: L/C,D/A,D/P,T/T
Supply Ability: 8000 Kilometer/Kilometers per Month
Place of Origin: Henan China
Brand Name: Jinshui
Model Number: BV2.5
Type: Insulated
Application: Indoors
Conductor Material: Copper
Conductor Type: Solid
Insulation Material: PVC
Packaging Detail: packing in coil,wooden drum

 

1.Range of Application

PVC insulated wires belong to the series of laying electric wires, which are mainly suitable for placing at the fixed places. It is widely used as connectors of drive, lighting, electronic equipment, instrument and communication equipment with rated voltage 450/750V (U0/U) or below. Parts of the plastic wires are used at the equipment with AC rated voltage 300/300V or below

 

2.Service Conditions

BV-105model not more than 105oC.Others not more than 75oC installation temperature not lower than 0oC.

 

1. Model and Name:see table 1              Table 1

Model

Name

BV

Copper Core PVC Insulation Wire

BLV

Aluminum Core PVC Insulation Wire

BV-90

Copper Core Heat-resistance 105oC PVC Insulation

 

BV BLV(BV-90)450/750V                Table 2

Nominal Section(mm2)

No/Dia.of Core(mm)

Max, O.D

 (mm)

Reference Weight(kg/km)

Conductor Resistance at 20oC≤(Ω/km)

Copper

Aluminum

Aluminum

Copper

1.5(A)

1/1.38

3.3

20.3

   

12.1

1.5(B)

7/0.52

3.5

21.6

   

12.1

2.5(A)

1/1.78

3.9

31.6

17

11.8

7.41

2.5(B)

7/0.68

4.2

34.8

   

7.41

4(A)

1/2.55

4.4

47.1

22

7.39

4.61

4(B)

7/0.85

4.8

50.3

     

6(A)

7/0.85

4.8

50.3

29

4.91

3.08

6(B)

7/1.04

5.4

71.2

   

3.08

10

7/1.35

7.0

119

62

3.08

1.83

16

7/1.70

8.0

179

78

1.91

1.15

25

27/2.04

10.0

281

118

1.20

0.727

35

27/2.52

11.5

381

156

0.868

0.524

50

19/1.78

13.0

521

215

0.641

0.387

70

19/2.14

15.0

734

282

0.443

0.268

95

19/2.52

17.5

962

385

0.320

0.193

120

37/2.03

19.0

1180

431

0.253

0.153

150

37/2.25

21.0

1470

539

0.206

0.124

185

37/2.52

23.5

1810

666

0.164

0.0991

240

61/2.25

26.5

2350

857

0.125

0.0754

300

61/2.52

29.5

2930

1070

0.100

0.0601

400

61/2.85

33.0

3870

1390

0.0778

0.0470

 

 

 

3.Technical Performance

1) The insulated cores and wires are good to pass the AV tests in the following Table after being put into water at the temperature of 20+5oCfor an hour,line are put into the water at the temperature 20+5oCfor an hour.They should be able to experience the AC voltage testing.

2) Outer power line is good at insulation property mechines property and non-inflammability with reliable quality attend convenient durability.The wires have good electrical insulation,mechanical and non-extersile property with hish releability and durability.

3) Finished wire should have wire,model and voltage signs.The wires should have secutive marks of manufacturers names,types of cables and rated voltage on the insulation or out sheath.

 

    Test Name

 

Voltage Test

For Insulated Core

          Test Item

          Test Value

     Rated Voltage of Wire

   300/500V

     1500

  450/750V

TestVoltageBased on Insulation Thickness

0.6mm and below

over 0.6mm

     2000

 

Voltage bring to bear on time not less than

   5 hours

 

Voltage Test for Wire

Testing voltage

    2000

 

Duration of voltage applied(min)

      5

 

 

 

 

 

 

 

 