Aluminum(Copper) split Concentric Cables

Port: | Qingdao |
Payment Terms: | L/C,D/A,D/P,T/T,Western Union,MoneyGram |
Supply Ability: | 500 Kilometer/Kilometers per Month |
Place of Origin: | Henan China |
Brand Name: | Yifang |
Model Number: | concentric cable |
Insulation Material: | PVC or XLPE |
Type: | Low Voltage |
Application: | Construction, Industrial, and Underground |
Conductor Material: | Copper or Alluminium |
Jacket: | PVC |
Certificate: | ISO,CCC,CE, SGS |
Delivery Detail: | Delivery on your requirements |
Packaging Detail: | non-returnable wooden steel drum |
1.Standards
IEC 60228: Conductors of insulated cables.
IEC 60502: Extruded solid dielectric insulated power cables for rated voltages from 1 kV up to 30 kV.
IEC 60811: Common test methods for insulating and sheathing materials of electric cables.
European Union Commission: SI 426: European Communities (dangerous substances) (classification, packaging, labellingand notification) regulation, 1992.
ISO: International Organization for Standardization
ISO 9000: Quality management and quality assurance standards – Guidelines for selection and use.
ISO 14000: Environmental management
VDE: VerbandDeutscherElektrotechniker:
VDE 0271: PVC-insulated cables with nominal voltages up to and including 6/10 kV.
VDE 0276: Application of cables and flexible cords in power installations.
Recommended values for the current carrying of cables with rated voltages U0/U up to 18/30 kV.
2.Application
These requirements cover Type USE and USE-2 (below-ground) and Type SE (above-ground) power cables for installation in accordance with Article 338 and other applicable parts of
the National Electrical Code (NEC). These cables are for the service-entrance and other (NEC) uses described in 1.4 – 1.8. In a multiple-conductor cable that is other than submersible-pump cable and does not have a grounding conductor
it is appropriate to have one circuit conductor without insulation. It is also appropriate for
a submersible pump cable to have a grounding conductor and for Type USE and USE-2 cables
to have an insulated grounding conductor. Each insulated conductor in these cables is rated for 600 V.
Type USE cable has thermoset insulation, except for the HDPE portion of HDPE-over-XLPE insulation where used for single-conductor Type USE cable. Type SE cable has thermoset or thermoplastic insulation.
3.Specification table
Nominal cross-section |
Strands number of conductor |
Insulation nominal thickness |
Concentric conductor |
Overall jacket nominal thickness |
Approx. overall diameter |
Approx. weight of compacted cable |
DC resistance at 20℃ |
Ambient temperature 30℃, frequency 40~60Hz |
||||
Min. diameter of single wire |
Max. number of single wire |
Operating temperature 90℃ |
Operating temperature 75℃ |
Operating temperature 60℃ |
||||||||
mm2 |
AWG |
Nos |
mm |
mm |
Nos |
mm |
mm |
kg/km |
Ω/KM |
A |
A |
A |
2.08 |
14 |
7 |
1.14 |
0.51 |
96 |
1.14 |
13.83 |
196 |
11.1954 |
30 |
26 |
20 |
2.63 |
13 |
7 |
1.14 |
0.51 |
96 |
1.14 |
14.26 |
222 |
8.8874 |
34 |
29 |
23 |
3.31 |
12 |
7 |
1.14 |
0.51 |
96 |
1.14 |
14.69 |
254 |
7.0513 |
38 |
33 |
26 |
4.17 |
11 |
7 |
1.14 |
0.51 |
96 |
1.52 |
16.08 |
313 |
5.5977 |
44 |
38 |
30 |
5.26 |
10 |
7 |
1.14 |
0.51 |
96 |
1.52 |
16.75 |
363 |
4.4322 |
51 |
44 |
35 |
6.63 |
9 |
7 |
1.52 |
0.51 |
96 |
1.52 |
19.25 |
472 |
3.5167 |
59 |
51 |
41 |
8.37 |
8 |
7 |
1.52 |
0.51 |
96 |
1.52 |
20.16 |
554 |
2.7874 |
68 |
59 |
47 |
10.55 |
7 |
7 |
1.52 |
0.51 |
96 |
1.52 |
21.26 |
656 |
2.2110 |
78 |
67 |
54 |
13.30 |
6 |
7 |
1.52 |
0.51 |
96 |
1.52 |
22.36 |
780 |
1.7533 |
90 |
77 |
62 |
16.77 |
5 |
7 |
1.52 |
0.51 |
96 |
1.52 |
23.83 |
937 |
1.3911 |
103 |
89 |
71 |
21.15 |
4 |
7 |
1.52 |
0.51 |
96 |
1.52 |
25.31 |
1126 |
1.1028 |
119 |
102 |
82 |
26.67 |
3 |
7 |
1.52 |
0.51 |
96 |
1.52 |
26.98 |
1363 |
0.8747 |
137 |
118 |
94 |
33.62 |
2 |
7 |
1.52 |
0.51 |
96 |
2.03 |
29.95 |
1704 |
0.6937 |
158 |
135 |
108 |
42.41 |
1 |
19 |
2.03 |
0.51 |
96 |
2.03 |
34.77 |
2198 |
0.5500 |
185 |
159 |
127 |
53.49 |
1/0 |
19 |
2.03 |
0.51 |
96 |
2.03 |
37.19 |
2671 |
0.4360 |
212 |
182 |
145 |
67.43 |
2/0 |
19 |
2.03 |
0.51 |
96 |
2.03 |
40.08 |
3266 |
0.3458 |
242 |
208 |
166 |
85.01 |
3/0 |
19 |
2.03 |
0.51 |
96 |
2.03 |
43.21 |
4003 |
0.2743 |
275 |
236 |
188 |
107.2 |
4/0 |
19 |
2.03 |
0.51 |
96 |
2.03 |
46.61 |
4920 |
0.2174 |
311 |
266 |
211 |