Aluminum Concentric Cable online shopping free shipping

Aluminum Concentric Cable online shopping free shipping
Port: Qingdao
Payment Terms: L/C,D/A,D/P,T/T
Supply Ability: 1000 Kilometer/Kilometers per Month
Place of Origin: China
Brand Name: SANHE
Model Number: 10,16,25
Insulation Material: PVC
Type: Low Voltage
Application: Construction
Conductor Material: Aluminum
Jacket: PVC
Color: Black
Product name: Aluminum Concentric Cable
Conductor: Alulminum
Standard: IEC60502
Insulation: PVC
Sheath: PVC
Packing: Wooden Drum
Voltage: 0.6/1KV
Sheath color: Black
Packaging Detail: Wood drum, or others as clien's requirement.

 

 

SCOPE

1.1 This specification is for LV PVC insulated single phase concentric cables with embedded communication cables to be used by KPLC for split prepayment metering. The cable shall carry both power and data in a single cable and shall have circular stranded aluminum conductors insulated for operation up to and including 1000 Volts between phases and 600 Volts to earth, concentric layers comprising of a blue PVC covered aluminum wires (combined neutral-earth conductor) and PVC insulated Two (2)-cores copper cables for data communication complete with a black PVC outer sheath.

1.2 The specification also covers inspection and test of the cables as well as schedule of guaranteed technical particulars to be filled, signed by the manufacturer and submitted for tender evaluation.

 

 Characteristics (as per KS 04-1022, BS 6360 and BS 7870-3.20)

Property

Cable Sizes

Phase 
Conductor

Nominal area,mm2

10

16

25

35

Form of conductors

Circular/compacted circular stranded

No.& approx. dia. of wires, No./mm

7/1.35

7/1.70

7/2.14

7/2.52

Min-Max. dia. of completed conductors, mm

*

4.6-5.2

5.6-6.5

6.6-7.6

Nominal diameter of conductors, mm

4.05

5.1

6.42

7.56

Minimum thickness of insulation, mm

1.55

1.55

1.60

1.65

Concentric neutral

Approx. no. of wires

7

11

14

16

Conductors

Approx. Diameter of wires, mm

1.50

1.50

1.50

1.50

Minimum lay lengths, mm

146.5

155

165

178

Thickness of over sheath, mm

1.4

1.4

1.5

1.6

Minimum thickness of over sheath at any point

1.09

1.09

1.17

1.20

Maximum conductor dc resistance per 1000m of cable at 20℃

Phase, Ω

3.08

1.15

1.20

0.868

Neutral-earth, Ω

4.61

3.08

1.91

1.20

Maximum weight of the complete conductor excluding insulations

*

43.9

69.5

96.4

Power frequency withstand voltage, for 5mins,kVrms

3.5

Insulation resistance at 500Vdc in 1mins at 20±5, MΩ/Km

8

6

6

5

*Manufacturer to state the design value based on the sizes of conductors specified

 

Equipment

 

Test

 PRODUCT LINE: 

 

 

 

Tags: , ,

Contact us

 

 

 

Search