Aerial Bundle Cable (Self Supporting and Supporting Core) 4x50mm2 Service Drop Quadruplex

Aerial Bundle Cable (Self Supporting and Supporting Core) 4x50mm2 Service Drop Quadruplex
Place of Origin: Henan China
Brand Name: Sanhe Cable
Model Number: ABC Cable
Type: Low Voltage
Application: Overhead
Conductor Material: Aluminum
Jacket: None
Insulation Material: XLPE
Selling Units: Single item
Single package size: 110X10X10 cm
Single gross weight: 0.24 KG
Package Type: Wood Drum
Package Preview: https://sc02.alicdn.com/kf/H18a6bfa100ed4e4eb372af6ce5183d45m.jpg_640x640.jpg
Product Description

 

1.Applications: 

Primarily used for overhead service applications such as street lighting. Outdoor lighting, and temporary service for construction. To be used at voltages of 600V phase-to-phase or less and at conductor temperatures not to exceed 75°c for polyethylene insulated conductors or 90°c for crossliked polyethylene(XLPE) insulated conductors.

 

2.Construction:

Concentric strand or compressed 1350-H19 conductor, poly- ethylene or cross linked polyethylene insulation,concentric strand AAC, ACSR or 6201 alloy neutral messenger.

 

3.Type of XLPE(PE) insulated abc cable (Quadruplex service drop)

XLPE(PE) insulatedabc cable (service drop)covers mainly three types:

Duplex Service Drop

Triplex Service Drop

Quadruplex Service Drop

The cable can be produced whose construction is phase conductor with neutral bare conductor or phase conductor with insulated neutral conductor , etc. And we can still produce the cables according to the request of customers.

 

4.Detaild Introduction of XLPE(PE) insulated abc cable (service drop) 

 

4.1  Duplex Service Drop

 

Applications

To supply 120 volt aerial service for temporary service at construction sites,outdoor or street lighting . For service at 600 volts or lower at a conductor temperature of 75 maximum.

 

4.2 Triplex Service Drop

 Applications

To supply power from the ulility`s lines to the consumer`s weatherhead. For service at 600 volts or less(phase to phase ) at a conductor temperature of 75 maximum for PE insulation or 90 maximum for XLPE insulation .

 

4.3 Quadruplex Service Drop

 Applications

Used to supply 3 phase power , usually from a pole-mounted transformer to the use`s servic head where connection to the service entance cable is made . To be used at voltages of 600 volts or less phase to phase and at conductor temperature not to exceed 75 for PE insulated conductors or 90 for XLPE insulated conductors.

 

5.Standards
1. B-230 Aluminum Wire, 1350-H19 for Electrical Purposes. 
2. B-231 Aluminum Conductors, Concentric-Lay-Stranded. 
3. B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR). 
4. B-399 Concentric-Lay_Stranded 6201-T81 Aluminum Alloy Conductors. 
5. B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR). 
6. Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474

 

6.Cable style as following :

 

 

Cores Nominal cross-sectional area Phase Conductors
insulation
Dia. Of cable R. of conductors at 20°C Break strength of conductor
Ω/km KN
3C+1C mm2 Thickness (mm) mm Phase cores Neutral cores Phase cores Neutral cores
3C+1C 3×25+54.6 1.4 23.57 1.2 0.630 16.6 16.6
3C+1C 3×35+54.6 1.6 26.08 0.868 0.630 16.6 16.6
3C+1C 3×50+54.6 1.6 28.15 0.641 0.630 16.6 16.6
3C+1C 3×70+54.6 1.8 32.15 0.443 0.630 16.6 16.6
3C+1C 3×70+54.6 1.8 32.15 0.443 0.630 16.6 16.6
3C+1C 3×70+70 1.8 32.75 0.443 0.500 20.5 20.5
3C+1C 3×95+70 1.8 35.78 0.32 0.500 20.5 20.5
3C+1C 3×120+70 1.8 37.93 0.253 0.500 20.5 20.5
3C+1C 3×120+70 1.8 37.93 0.253 0.500 20.5 20.5
3C+1C 3×120+95 1.8 39.26 0.253 0.343 27.5 27.5
3C+1C 3×150+95 1.9 41.81 0.206 0.343 27.5 27.5

 