XLPE SWA Armoured Electrical 4 Core Cable
Application Features:
1. Cable conductor allowable long-term maximum operating temperature is 90 ℃.
2. Short circuit (the longest duration no more than 5 seconds ), the conductor temperature does not exceed 250 ℃.
3. While laying process, the cable should not below 0℃, otherwise the cable needs to be pre-heated.
4. The minimum bend radius of the cable :
(1) Three Cores Cable: no less than 15 times of the cable external diameter;
(2) Single Core Cable: no less than 20 times of the cable external diameter.
We are capable of meeting the most strict delivery schedules according to per purchase order. Meeting the deadline is always the top priority as any delay in the delivery of cable can contribute to overall project delay and cost overrun.
Cable is supplied in wooden reels, corrugated boxes and coils. Cable ends are sealed with BOPP self adhesive tape and non-hygroscopic sealing caps to protect the cable ends from moisture. The required marking shall be printed with a weather-proof material on the outsides of drum according to customer's requirement.