Single-core XLPE – insulated cables with PVC sheath 6/10kv  8.7/15 kv 12/20 18/30KV  Medium Voltage Power Cable
 
Product Description
 
|  | 
| 
Circular bare copper-conductor of stranded wires to HD 383Inner semi-conducting coatingConductor insulation of cross-linked Polyethylene (XLPE), PE-compound DIX8 to HD 620.1Outer extrusion of semi-conducting coating spliced with the insulationWrapping of conductive materialShield: Braiding of copper wires with one or two tape(s) applied helicallyWrappingPVC outer jacket, compound DMV6 to HD 620.1Jacket color: Red | 
| 
| Suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch boards and power stations. Due to the good laying characteristic, this cable can also be installed in difficult in difficult line guide ways. The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.
 |  | 
 
| 
XLPE-insulated power cables to DIN VDE 0276 part 620, HD 620 S1 and IEC 60502Temperature RangeDuring installation up to -5°C/+23°F
Operating TemperatureMax. +90°C/+194°F
Short Circuit Temperature+250°C/+482°F (short circuit duration up to 5 sec.)
Nominal VoltagesU0/U 6/10 kV, 12/20 kV, 18/30 kV
 | 
Operating Voltages for6/10 kV = max. 12 kV
 12/20 kV = max. 24 kV
 18/30 kV = max. 36 kV
Test Voltages for6/10 kV = 15 kV
 12/20 kV = 30 kV
 18/30 kV = 45 kV
Minimum Bending RadiusDuring installation max. 15x cable Ø
Power Ratings TableSee Technical Information
 
 | 
| Code-Designation for Power Cables with PVC or XLPE Insulation 
 | 
| 
| Design | Identification of Design | Explanations |  
| Conductor | N | According to VDE Standard (No abbreviation for copper conductor)
 |  
| A | Aluminum conductors |  
| Y | Insulation of thermoplastic Polyvinyl chloride (PVC) |  
| 2X | Insulation cross-linked Polyethylene (XLPE) |  
| Concentric Conductor, Shielding | C | Concentric conductors of copper wires and copper tape, helically wounded |  
| CW | Concentric conductors of copper wires in wave conal formation and and copper tape, helically wounded |  
| CE | Concentric conductors of copper wires and copper tape over each individual conductor, helically wounded |  
| Shielding | S | Shielding of copper wires and copper tape, helically wounded |  
| SE | Shielding of copper wires and copper tape over each individual conductor, helically wounded |  
| (F) | Longitudinally water-proof shielding |  
| Armor | B | Armor of steel tape |  
| F | Armor of galvanized flat steel wires |  
| G | Counter helix of galvanized steel tape |  
| Jacket | K | Lead jacket |  
| Outer Jacket | Y | PVC jacket |  
| 2Y | PE jacket |  
| Cable for U0/U 0.6/1 kV are additionally designated with |  
|  | -J | Cables with green-yellow (green-natural) conductor are marked with protective conductor |  
| -O | Cables without green-yellow (green-natural) conductor are marked without protective conductor |  |