Copper core XLPE insulated power cable

| Port: | Qingdao | 
| Payment Terms: | L/C,D/P,T/T | 
| Supply Ability: | 28000 Meter/Meters per Week | 
| Place of Origin: | Henan China | 
| Brand Name: | ZMS Cable | 
| Model Number: | power cable | 
| Insulation Material: | PVC | 
| Type: | Low Voltage | 
| Application: | Construction | 
| Conductor Material: | Aluminum | 
| Jacket: | PVC | 
| Packaging Detail: | Drum | 
APPLICATION
These XLPE insulated and LSZH sheathed cables are generally used for fixed installation. Suitable for building wiring, especially in areas where smoke and fume emissions may cause a potential threat to life but not for burial in the ground, either directly or in ducts.
STANDARD
Basic design to BS 8573:2012
FIRE PERFORMANCE
| Flame Retardance (Single Vertical Wire Test) | BS EN 60332-1-2:2004 | 
| Reduced Fire Propagation (Vertically-mounted bundled wires; cable test) | BS EN 60332-3-24:2009 (cat. C) | 
| Halogen Free | BS EN 50267-2-1 | 
| Minimum Smoke Emission | BS EN 61034-2 | 
| Spark Test | BS EN 62230 | 
VOLTAGE RATING
600/1000V
CABLE CONSTRUCTION
Conductor: Annealed copper conductor, strand according to BS EN 60228 class 2.
Insulation: XLPE type GP8 according to BS 7655-1.3. HEPR type GP6 according to BS 7655-1.2, or crosslinked polyolefi n material type EI 5 according to BS EN 50363-5 can be offered as option.
Inner Covering option: The laid up cores may be coverd by an optional extrued inner covering or separating tape. It shall be possible to separate the cores easily.
Outer Sheath: Thermoplastic LSZH type LTS 4 according to BS 7655-6.1.
Outer Sheath option: UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE
Insulation Colour:
Blue, brown black and grey,
Alternatively, green-and-yellow, brown, black, grey
Sheath Colour: Black, other colours can be offered upon request.
PHYSICAL AND THERMAL PROPERTIES
Maximum temperature range during operation (XLPE): 90°C Maximum short circuit temperature (5 Seconds): 250°C Minimum bending radius:
Circular copper conductors(up to 25mm2): 4 x Overall Diameter
Circular copper conductors(above 25mm2): 6 x Overall Diameter
Shaped copper conductors: 8 x Overall Diameter
CONSTRUCTION PARAMETERS
| Conductor | Nominal Insulation Thickness | Nominal Sheath Thickness | |
|---|---|---|---|
| No.of Coresx Cross Section | Class of Conductor | ||
| No.xmm2 | mm | mm | |
| 4×1.5 | 2 | 0.7 | 1.8 | 
| 4×2.5 | 2 | 0.7 | 1.8 | 
| 4×4.0 | 2 | 0.7 | 1.8 | 
| 4×6.0 | 2 | 0.7 | 1.8 | 
| 4×10 | 2 | 0.7 | 1.8 | 
| 4×16 | 2 | 0.7 | 1.8 | 
| 4×25 | 2 | 0.9 | 1.8 | 
| 4×35 | 2 | 0.9 | 1.8 | 
| 4×50 | 2 | 1.0 | 1.8 | 
| 4×70 | 2 | 1.1 | 2.0 | 
| 4×95 | 2 | 1.1 | 2.1 | 
| 4×120 | 2 | 1.2 | 2.3 | 
- Next: PVC coat power cable 0.6/1kv fr cu/xlpe/pvc 90mm Cu/Al Conductor