600v Aluminum Conductors HDPE insulation Parallel Aerial Cable

600v Aluminum Conductors HDPE insulation Parallel Aerial Cable
Port: Qingdao
Payment Terms: L/C,T/T,Western Union,MoneyGram,Parallel Aerial Cable
Supply Ability: 30 Kilometer/Kilometers per Day Parallel Aerial Cable
Place of Origin: Henan China
Brand Name: Hongda
Model Number: Parallel Aerial Cable
Insulation Material: PE
Type: Low Voltage
Application: Overhead
Conductor Material: Aluminum
Jacket: NO
Phase conductors: 2, 3 or 4 longitudinal ridges
Messenger: Stranded aluminum alloy wire
Insulation: High Density Polyethylene
Rated Voltage: 0.6/1KV
Size: 16mm2, 25-120mm2
Standard: ASTM
Continuous operation: 70°C
Short circuit: 135°C, duration up to 5s
Laying up: Insulated conductors are laid up around the messager
Product name: 600v Aluminum Conductors HDPE insulation Parallel Aerial Cable
Delivery Detail: 12 days, depend on the quantity
Packaging Detail: Packaging in roll or wooden drum for 600v Aluminum Conductors HDPE insulation Parallel Aerial Cable

600v Aluminum Conductors HDPE insulation Parallel Aerial Cable

Product Description

Parallel Aerial Cable

0.6/1kV Service Drop Aerial Cable Parallel Aluminum Conductors

  • Parallel Aerial Cable.
  • Aluminum Conductors.
  • High Density Polyethylene or Crosslinked Polyethylene Insulation.

Parallel Aerial Cable Rated Voltage:

Uo/U = 0.6/1kV, Um = 1.2kV

 

Parallel Aerial Cable Application:

Used as secondary overhead distribution cable at voltages of 600V or less phase to phase and at conductor temperatures not to exceed 90°C for crosslinked polyethylene (XLP) insulated conductors.

Parallel Aerial Cable Highest permissible conductor temperature:

continuous operation : 70°C

short circuit ( duration up to 5s ): 135°C

Lowest recommended temperature during laying: -20°C

 

Parallel Aerial Cable Construction:

Conductors are concentrically stranded, compressed 1350-H19 aluminum, insulated with crosslinked polyethylene (XLP). Neutral messengers are either 6201 aluminum alloy or ACSR. The phase conductors are paralleled with the neutral messenger, and bound together with binder wire (1350-H19 aluminum alloy, #10, covered with high density polyethylene). Multi-conductor cables incorporate stripes or ridges for phase identification.

Parallel Aerial Cable Identification of cores:

Phase conductors: 2, 3 or 4 longitudinal ridges

Optional conductor: no ridges

Parallel Aerial Cable Strandards:

  • ASTM B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • ASTM B-231 Aluminum Conductors, Concentric-Lay-Stranded.
  • ASTM B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
  • ASTM B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
  • Meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.

Notes
+Ampacity figures for black insulation only (gray will vary slightly).
Conductor temperatures of 90°C for XLP; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

++For ACSR shows Al/Stl.

Certificates, Approvals:

CCC, ISO

 

The cable does not contain any substances on the reach list.

All substances of the cable meet the requirements of RoHS directive.

 

CUSTOMS CODE / HS CODE:  85444921

Item #

Phase
Conductor
Size
(AWG)

Phase
Conductor
Stranding

Phase
Conductor
Insulation
Thickness
(mils)

Bare
Neutral
Messenger
Size
(kcmil)

Bare
Neutral
Messenger
Stranding++

Bare
Neutral
Messenger
Rated
Strength

Weight
XLP
(lb/MFT)

Allowable
Ampacities
XLP+

                 
Mendocina 2/0 7 60 2/0 6/1 5310 701 205
Helena 1/0 7 60 1/0 6/1 4380 570 180
Roosevelt 3/0 17 60 3/0 6/1 6620 848 235
Tonto 4/0 18 60 4/0 6/1 8350 1049 275

More informations and questions, pls contact with Vivian Yuan. (Email: sale04 @ zzhongdacable.com.cn, WhatsApp/Wechat: 0086-15838290725, Skype: xinyuanyy)

Parallel Aerial Cable Properties:

 

Product name

AMKA

1X16+25

AMKA

3X16+25

AMKA

3X25+35

AMKA

3X35+50

AMKA

3X50+70

AMKA

3X70+95

AMKA

3X120+95

AMKA

4X16+25

AMKA

3X25+16+35

AMKA

3X35+16+50

Construction data (1)

Diameter over bare conductor

mm

4.4 4.4 5.5 6.8 8.0 9.6 12.7 4.4 5.8 6.8

Diameter over messenger

mm

5.8 5.8 6.8 8.0 9.6 11.3 11.3 5.8 6.8 8.0
Construction of messenger 7×2.30 7×2.30 7×2.70 7×3.12 7×3.76 7×4.36 7×4.36 7×2.30 7×2.70 7×3.12

Effective diameter in wind (4)

mm

11 20 23 27 31 36 42 22 25 29
Weight

aluminum

kg/km

100 185 285 390 540 775 1185 225 330 440

cable

kg/km

135 270 390 530 700 1000 1500 330 465 610
Delivery data

Strandard delivery lenght

m

2000 1000 1000 1000 1000 500 500 1000 1000 1000
Standard delivery drum K11 K12 K14 K16 K18 K14 K18 K12 K14 K16

Weight (1)       cable+drum

kg

325 360 505 725 930 615 980 420 580 805
Mechanical data (2)

Minimum permissible bending radius during laying

m

0.28 0.42 0.50 0.58 0.66 0.78 0.92 0.42 0.50 0.58

Minimum permissible bending radius at final installation (3)

m

0.20 0.30 0.35 0.41 0.47 0.55 0.65 0.30 0.35 0.41

Minimum tensile strength of the messenger

kN

7.4 7.4 10.3 14.2 20.6 27.9 27.9 7.4 10.3 14.2
Initial modulus of elasticity of the messenger    – N/mm2 55000
Final modulus of elasticity of the messenger    – N/mm2 63000
Coefficient of linear expansion of the messenger     – 1/K 23×10-6
Eletrical data

Maximum DC resistance of phase conductor

conductor at 20°C

Ω/km

1.91 1.91 1.20 0.868 0.641 0.443 0.253 1.91 1.20 0.868

AC resistance of phase and neutral conductor

conductor at 70°C

Ω/km

2.3 2.3 1.4 1.0 0.77 0.53 0.30 2.3 1.4 0.3

Maximum DC resistance of the messenger

conductor at 20°C

Ω/km

1.38 1.38 0.986 0.720 0.493 0.363 0.363 1.38 0.986 0.720

Inductance (1)

mH/km

0.29 0.35 0.34 0.34 0.33 0.31 0.30 0.35 0.34 0.34
Current ratings (2)

In free air

conductor at 70°C

A

75 70 95 115 140 180 250 70 90 115

Short circuit currents (2)

Maximum permissible short circuit current for one second

Phase conductor (5)     – kA 1.0 1.0 1.6 2.3 3.2 4.5 7.8 1.0 1.6 2.3
messenger (6)     – kA 1.5 1.5 2.1 3.0 4.3 5.9 5.9 1.5 2.1 3.0

 

  • (1) Approximate value.
  • (2) See the basic assumptions at general information of products.
  • (3) Final installation with careful single bending into final position.
  • (4) The effective diameter in wind is equal to the length of measuring tape wrapped around the cable divided by the value 3.1416(π).
  • (5) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 135°C.
  • (6) Initial temperature of messenger before short circuit 70°C, final temperature of messenger after short circuit 135°C.

 

 

 

Packaging & Shipping

Packing: 

Steel wooden drum (fumigation)
Cable length in each drum: 500m/1000m or as per actual cable length requirements.

Small size packing in roll Big size packing in drum

Drum size:
As per cable length and container size
*In order to quote you accurate price, kindly tell us your needed cable length quantity. Larger quantity, more discount benefit ready for you!

Shipping:
Port: Tianjin, Qingdao, or other ports as per your requireents.

Sea freight:
FOB/C&F/CIF quotation are all available.

 

 

Company Information

Company Profile

Hongda cable Co., Ltd. is one of the most professional cable & wire producer under modern enterprise system in China, which was founded in 1988, integrating scientific research, development, production and sales. The company mainly produces 1-35 kV power cable, 35mm cable in electrical wires, AAC, AAAC, ACSR.

Our advantages

1.  With more than 17 years manufacturing experience, our products are strictly in accordance with ISO, CE, UL and BV;

2.  Good cost-control system, with highly-competitive prices;

3.  Strong and Professional R&D team to meet your specific needs;

4.  Fast delivery&reliable products are always the reason why you choose us.

 

Contact Information

Contact information

 

Any needs or question ,please contact us ,we will be more pleasure to service you.

 

We are looking forward to your inquiry and nice cooperaton.

 

Tags: , ,

Contact us

 

 

 

Search

You May Like

  • No related articles