3x70mm2 AAC XLPE-ABC cable

Port: | Qingdao |
Payment Terms: | L/C,D/A,D/P,T/T |
Supply Ability: | 2000 Kilometer/Kilometers per Month |
Place of Origin: | Henan China |
Brand Name: | Jinshui |
Model Number: | overhead cable |
Insulation Material: | XLPE |
Type: | Low Voltage |
Application: | Overhead |
Conductor Material: | Aluminum |
Jacket: | XLPE |
Packaging Detail: | wooden drum,steel-wooden drum |
Instruction For ABC Cable
Triplex service drop
To supply power from the utility’s lines to the consumer’s weatherhead.For service at 600 volts or less (pahse to phase) at a conductor temperature of 75°Cmaximum for polyethylene insulation or 90°C maximum for crosslinked insulation.
Construction
Ref. No. |
Description |
Unit |
Data |
8.1 |
LVAERIAL BUNDLE CABLE (600/1000V) 2×35+35mm2 |
|
|
1 |
Manufacturer |
Zhengzhou Jinshui Industry&Commerce Co.,Ltd |
|
2 |
Standards |
IEC60502, DIN 48201 |
|
3 |
Nominal voltage (Uo/U) |
KV |
0.6/1 |
4 |
Material of conductor phase neutral |
|
AAC AAAC |
5 |
Cross-section of phase conductor. |
mm2 |
35 |
6 |
No. of strand of Phase conductor/Minimum Strand Diameter |
|
7/2.56 |
7 |
Diameter of phase conductor |
mm |
7.68 |
8 |
Thickness of insulation XLPE |
mm |
1.4 |
9 |
External diameter of individual core |
mm |
10.45 |
10 |
Cross sectional of neutral wire |
mm² |
35 |
11 |
No. of strand /Average Strand Dia. In mm.(Neutral) |
|
7/2.52 |
12 |
Modulus of elasticity |
N/mm2 |
60000 |
13 |
Diameter of neutral wire |
mm |
7.56 |
14 |
Ultimate tensile strength of suspension wire |
KN |
9.73 |
15 |
Thickness of suspension wire covering |
mm |
BARE |
16 |
Overall diameter of bundle |
mm |
19.56 |
17 |
Total weight of bundle per km |
kg/km |
355 |
18 |
Maximum DC resistance / km at 20°C – Phase conductors – Neutral conductor |
Ω /km Ω /km |
0.868 0.9669 |
19 |
Working inductance |
MH/km |
0.2059 |
20 |
Working capacitance |
mF/km |
0.0004136 |
21 |
1 sec. Thermal short circuit current (maximum conductor temperature 130°C, final conductor |
KA |
1.8 |
22
23 |
Maximum continuous current at 35°C ambient temperature 0.6m/sec wind and 90°C conductor temperature. – Phase conductors – Neutral conductor Zero sequence impedance |
A A |
138 100 |
Ω/km |
1.294 |
||
24 |
Standard unjointed length on drum |
m |
1000 |
1. Are you the factory or trading company?
We are the manufacturer and 13 years gold supplier on alibaba.We are engaged in exporting cables for nearly 15 years.
2. When can I get the price?
We usually quote within 6 hours after we get your inquiry. If you are very urgent to get the price, please call us or tell us in your e-mail so that we will regard your inquiry priority.
3. How can I get a sample to check your quality?
After price confirmation, you can require for samples to check our quality. Sample is free, but the freightcharge should be paid.
4. What is the payment terms?
30% deposit by T/T,70% T/T after checking the copy of B/L. Or irrevocable L/C at sight .
5. What about the lead time for mass production?
Honestly, it depends on the order quantity and the season you place the order. Generally speaking, we suggest that you start inquiry two months before the date you would like to get the products at your country.
Contact us