3 phase cable 11 kV, metallic screen shielded cable, CU/XLPE/CTS/SWA/STA/PVC
Construction:
1.Phase conductor: Compacted stranded copper conductor
2.Phase conductor screen: Semi-conductor
3.Insulation: XLPE
4.Insulation screen: Semi-conductor
5.Metallic shield: Copper tape
6.Ground conductor: Bare stranded copper conductor
7.Fillers
8.Binding tape
9.Inner cover: LSHF
10.Wire armour: Galvanised steel wire
11.Tape armour:Galvanised steel tape
12.Outer sheath: PVC/PE/LSOH
Applications
Three phase cable 15 kV class, 3 + 3 cores with metallic screen shielded for use in underground mining, halogen free, flame retardant and low smoke emission
Standards
International: IEC 60502-2, IEC 60228
China: GB/T 12706.2-2008
Other standards such as BS,DIN and ICEA upon request
Technical data
Rated voltage: 1.8/3kV, 6/10kV, 8.7/15kV, 12/20kV, 18/30kV, 21/35kV, 26/35kV
Maximum Conductor Temperature: under normal (90°C), emergency (130°C) or short circuit no more than 5 s (250°C) conditions.
Min. Ambient Temp. 0°C, after installation and only when cable is in a fixed position
Min. Bending Radius: 20 x cable O.D for single-core non-armoured cables
15 x cable O.D for single-core armoured cables
15 x cable O.D for multi-core non-armoured cables
12 x cable O.D for multi-core armoured cables