2XS2Y A2XS2Y Cable 3.6/6 kV, 8.7/15 kV, 20/35 kV IEC 60502-2

2XS2Y A2XS2Y Cable 3.6/6 kV, 8.7/15 kV, 20/35 kV IEC 60502-2
Port: Qingdao, China or any other Port
Payment Terms: L/C,D/A,D/P,T/T
Supply Ability: 1000 Kilometer/Kilometers per Month
Place of Origin: Henan China
Brand Name: Yifang
Model Number: Copper/XLPE/SWA/PVC
Insulation Material: XLPE
Type: Medium Voltage
Application: Construction, Power Station. Overhead
Conductor Material: Copper, Aluminum
Jacket: PVC
Color: As request
Standard: BS IEC ASTM DIN
Product name: power cable
Conductor: Bare Copper
Certificate: ISO9001
Packing: Wooden-steel Drum
Delivery Detail: according to your quantity, usually Approx.30days
Packaging Detail: wooden drums or steel wooden drums or as customer's requirement
Uo/U – 3.6/6 kV, 8.7/15 kV, 20/35 kV IEC 60502-2
The single-core cables with insulation of cross-linked polyethylene (XLPE) are designed for transfer and distribution of electrical power with nominal voltage Uo/U 3.6/6kV; 8.7/15kV Ë 20/35 kV and frequency 50 Hz in urban and district elec­trical networks and for electrical supply of transformer's substations, small and medium industrial plants.
 
They are suitable for use in distribution installations, electric power stations and industrial systems. The cables are for fixed assembly in lines with unlimited difference levels, indoor installations, in cable ducts, conduits and shafts, over shelves and grills directly underground in ditch and outdoor shelter
Cable construction
Construction
According to IEC 60502
Conductor
Cu and Al stranded compacted, according to IEC 60228 class 2
Inner semi-conductive layer
semi-conductive XLPE compound
Insulation
XLPE compound
Outer semi-conductive layer
semi-conductive XLPE compound and semi-conductive tape or extruded semi-conductive XLPE compound
Metal screen
Cu wires concentrically laid and one contact of Cu tape with thickness of 0.1mm.
Separating layer
Layer of plastic tape
Sheath
PE compound
type ST7 according to IEC 60502
Color
black
Technical data
Conductor resistance at 20°C
According to BDS904
(IEC60228) class 2
Operating temperature
90°C continuous operation
Overload temperature
130°C /100h per year max./
Short circuit temperature
250°C /5 s max./
Nominal voltage Uo/U:
6/10;12/20 kV
Highest system voltage
6/10; 12/20 kV
Uo/U, no more than
12kV; 24kV kV
Test voltage Uo/U
6/10; 12/20 kV
AC (≈) – 5 min
15kV; 30kV kV
DC (=) – 15 min
48kV; 96kV kV
Level of partial discharge at 2*Uo
Bending radius, min
Temperature of laying
 max. 5 pC

15x D cable
no less than – 20°C
Temperature of
exploitation
 -30 to 50°C
Tests
according to IEC 60502-2 or
Force of strain in laying N max.
where:
 
 
Al cores – 30*n*S core Cu cores – 50*n*S core n- number of cores and
-S-cross-section of
conductors in mm
Tags: , ,