Product description of 120mm wire cable
1. NO.of Core: 2 3 4 5 3+1 3+2 4+1 5 etc.
2. Power Wire Rated voltage: 0.6~132kv
3. Nominal Cross-sectional area: 1.5~400mm2
4. Power Cable Test voltage(a.c): 3.5kv/5min
5. Standards: GB/12706 or IEC
6. Power Cable Application: Suitable for use in power distribution lines or fixed
7. Power Cable Operating Characteristics:
1).Max.permissible continuous operating temperature of conductor(PVC/XLPE): 70°C/90°C
2). Max.short-circuit temperature of conductor shall not exceed(5s maximum duration) XLPE:250°C
3). The ambient temperature under installation shall not be below 0°C
4). Bending radius:
A, Common bending radius:
a. ≥20D (1and 2cores)
b. ≥15D (3 cores)
c. ≥15D (2 cores with armor)
d. ≥12D (4,5,3+1,4+1,3+2 cores with armor)
D= outer diameter
B, Bending radius for the section which near the junction and connector:
a. ≥15D (1 and 2 cores)
b. ≥12D (3, 4,5,3+1,4+1,3+2 cores)
c. ≥12D (2 cores with armor)
d. ≥10D (3, 4, 5, 3+1,4+1,3+2 cores with armor)
Technical Data:
Four cores:
3+1 cores:
Factory Show:
Package And Transportation:
We are specializing in the production of cables and wires,the spirt of us is "quality first, reputation first, service first, customer first"