1.5mm2 2.5mm2 4mm2 6mm2 PVC Insulated Electric Wire Cable Flexible Building Wires
Features
|
ENERGY CABLES Building & Construction Building Wire Single Core, Copper |
APPLICATION
|
For separate earth conductors. For switchboard and control panel wiring. For fixed wiring within other enclosures or apparatus where the cable is not accessible without the use of tools. |
STANDARD |
IEC60227-3:1997 |
|
CODEDESIGNATION |
60227 IEC 01 (BV, Cu/PVC) |
|
|
VOLTAGE |
450/750V |
|
|
CONDUCTOR |
Copper 1.5 – 185mm2 |
|
|
INSULATION |
PVC/C See below for colour options |
|
|
MAX. OPERATING TEMP. |
70°C |
Technical Parameters
Welcome to inquiry about other special types and OEM accepted.
Thechnical Prameters
|
ITEM NUMBER |
CONDUCTOR |
NOMINAL INSULATION THICKNESS /mm |
APPROX. OVERALL DIAMETER /mm |
APPROX. MASS
kg/km |
MINIMUM INSTALLED RADIUS /mm |
||||
|
mm2 |
No./mm |
||||||||
|
1000xxx |
1.5 |
1/1.38 |
0.7 |
2.78 |
21.1 |
18 |
|||
|
1001xxx |
1.5 |
7/0.52 |
0.7 |
2.96 |
21.9 |
18 |
|||
|
1002xxx |
2.5 |
1/1.78 |
0.8 |
3.38 |
32.9 |
20 |
|||
|
1003xxx |
2.5 |
7/0.68 |
0.8 |
3.64 |
34.9 |
20 |
|||
|
1004xxx |
4 |
1/2.25 |
0.8 |
3.85 |
48.0 |
23 |
|||
|
1005xxx |
4 |
7/0.85 |
0.8 |
4.15 |
49.9 |
23 |
|||
|
1006xxx |
6 |
1/2.76 |
0.8 |
4.36 |
67.9 |
26 |
|||
|
1007xxx |
6 |
7/1.04 |
0.8 |
4.72 |
70.2 |
26 |
|||
|
1008xxx |
10 |
1/3.56 |
1.0 |
5.56 |
111.4 |
33 |
|||
|
1009xxx |
10 |
7/1.34 |
1.0 |
6.02 |
114.8 |
33 |
|||
|
1010xxx |
16 |
7/1.68 |
1.0 |
7.04 |
171.1 |
42 |
|||
|
1011xxx |
25 |
7/2.12 |
1.2 |
8.76 |
268.9 |
53 |
|||
|
1012xxx |
35 |
7/2.50 |
1.2 |
9.90 |
363.1 |
59 |
|||
|
1013xxx |
50 |
19/1.76 |
1.4 |
11.60 |
488.8 |
70 |
|||
|
1014xxx |
70 |
19/2.12 |
1.4 |
13.40 |
690.1 |
80 |
|||
|
1015xxx |
95 |
19/2.50 |
1.6 |
15.70 |
954.8 |
94 |
|||
|
1016xxx |
120 |
37/2.00 |
1.6 |
17.20 |
1174.9 |
103 |
|||
|
1017xxx |
150 |
37/2.22 |
1.8 |
19.14 |
1448.7 |
115 |
|||
|
1018xxx |
185 |
37/2.48 |
2.0 |
21.36 |
1805.7 |
128 |
|||
|
• xxx=001 for Black |
• xxx=002 for Blue |
• xxx=003 for Brown |
• xxx=004 for Grey |
||||||
|
• xxx=005 for Red |
• xxx=006 for Green/Yellow |
• xxx=007 for Green |
• xxx=008 for Yellow |
||||||
Technical Prameter – Continued
|
CONDUCTOR |
CURRENT RATING (a) |
ELECTRICAL CHARACTERISTICS |
||||
|
Nominal Area mm2 |
FIXED WIRING |
Maximum DC Resistance @20℃ Ω/km |
Maximum AC Resistance @90℃ Ω/km |
Equivalent Star Reactance (trefoil) Ω/km |
Single Phase Voltage Drop (trefoil) @90℃ mV/Am |
|
|
Unenclosed In Air |
Conduit In Air |
|||||
|
1.5 |
16 |
16 |
13.6 |
17.3 |
0.157 |
34.7 |
|
2.5 |
23 |
24 |
7.41 |
9.45 |
0.143 |
18.9 |
|
4 |
31 |
32 |
4.61 |
5.88 |
0.137 |
11.8 |
|
6 |
40 |
41 |
3.08 |
3.93 |
0.128 |
7.87 |
|
10 |
54 |
54 |
1.83 |
2.33 |
0.118 |
4.68 |
|
16 |
72 |
70 |
1.15 |
1.47 |
0.111 |
2.95 |
|
25 |
97 |
94 |
0.727 |
0.927 |
0.106 |
1.87 |
|
35 |
119 |
112 |
0.524 |
0.668 |
0.101 |
1.35 |
|
50 |
146 |
138 |
0.387 |
0.494 |
0.0962 |
1.01 |
|
70 |
184 |
170 |
0.268 |
0.342 |
0.0917 |
0.710 |
|
95 |
230 |
212 |
0.193 |
0.247 |
0.0904 |
0.528 |
|
120 |
267 |
242 |
0.153 |
0.197 |
0.0870 |
0.431 |
|
150 |
308 |
282 |
0.124 |
0.160 |
0.0868 |
0.365 |
|
185 |
358 |
320 |
0.0991 |
0.129 |
0.0862 |
0.329 |
|
240 |
428 |
361 |
0.0754 |
0.0991 |
0.0847 |
0.283 |
(a) Based on 40℃ ambient air temperature.
The above information is from the following sources:
• IEC 60287 Electric cables – Calculation of the current rating (all Parts)
• IEC 60364 Electrical installations of buildings
• IEC 60228 Conductors of insulated cables
Do not put in direct contact with polystyrene, polyurethane or similar thermal insulation materials.
Test system
Certificates
All our products are approved BY CE, CCC ,ISO9001 and ISO14001