XLPE/PVC Insulated( 70mm copper cable 1)
Configuration
Conductor: Plain annealed copper (CU) or plain aluminium (AL) as specified in AS/NZS 1125.
Inner Insulation: Cross-linked Polyethylene (XLPE) as specified in AS3808.
Outer Insulation: Flame retardant Polyvinyl Chloride PVC V90 as specified in AS3808.
Sheath Colour: Black or Orange.
Electrical Characteristics
Rated Voltage: 0.6/1 kV
Conductor Operating Temp: -40ºC ~ 90ºC
Max Short Circuit Temp: -40ºC ~ 90ºC
Minimum Bending Radius: 15x cable O.D during installation, 12x cable O.D after installation
NB.
– The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints,terminations and environmental conditions.
– The cables should not be flexed when either the ambient or cable temperature is below 0ºC.
Standards
AS / NZS5000.1, AS / NZS1125, AS / NZS3808
0.6 / 1kV CU / XLPE / PVC / V90
Low voltage XLPE cable Steel Wire or Steel Tape Armoured( 70mm copper cable 2)
Configuration
Conductor: Plain annealed copper (CU) or plain aluminium (AL) as specified in AS/NZS 1125.
Inner Insulation: Polyvinyl Chloride PVC as specified in AS3808.
Armour: Green & Yellow.
Outer Insulation: Flame retardant Polyvinyl Chloride PVC V90 as specified in AS3808.
Shealth Colour: Black & Orange.
Electrical Characteristics
Rated Voltage: 0.6/1 kV
Conductor Operating Temp: -25ºC ~ 75ºC MAX 90ºC
Max Short Circuit Temp: 160ºC for 5 seconds
Minimum Bending Radius: 18x cable O.D during installation,
15x cable O.D after installation
0.6 / 1kV CU / PVC / SSWA / PVC / V90
Low Voltage Multi Cores XLPE Cable( 70mm copper cable 3)
0.6 / 1kV CU / XLPE / PVC V90
Installation
Suitable for installation indoor/outdoor, enclosed in conduit or in underground duct where not subject to mechanical force or damage and/or where conditions of overload may occur. Additional protection is available for UV, low smoke zero halogen (LS0H) and Flame Retardant (FR) properties where required.
Configuration
Conductor: Pain annealed copper of the type specified in AS/NZS 1125.
Insulation: Cross-linked polyethylene compound XLPE as specified in AS3808.
Laying-up: Cores are laid up with a right-hand direction of lay & non-hygroscopic filler where necessary.
Sheath: Continuous polyvinyl chloride compound PVC V90 as specified in AS3808.
Core Identification
2C + E Phase core: Red Neutral core: Black Earth Core: Green/Yellow
3C + E Phase core: Red, White, Blue Earth Core: Green/Yellow
4C + E Phase core: Red, White, Blue Neutral core: Black Earth Core: Green/Yellow
Sheath: Orange (standard) or Black (optional ultraviolet radiation stabilized).
Technical Data
Rated Voltage: 0.6/1kV
Conductor Operating Range: -40ºC ~ 90ºC MAX 90ºC
Max Short Circuit Temp: 250ºC for 5 seconds
Minimum ambient temperature 0ºC, after installation and only when cable is in a fixed position.
Minimum bending radius
Stranded conductors:
9x cable O.D during installation
6x cable O.D after installation
Compacted conductors:
12x cable O.D during installation
8x cable O.D after installation
Copper Conductor Cable,without armoured Cable( 70mm copper cable 4)
SINGLE CORE, COPPER CONDUCTOR,
SCREENED AND UNARMOURED CABLE
APPLICATION:
Mains enclosed in conduit, buried or underground
ducts for industrial plants, buildings and transformers
where not subject to mechanical damage.
Three Core Copper Conductor cable, without armoured ( 70mm copper cable 5)
THREE CORE, COPPER CONDUCTOR, SCREENED
& UNARMOURED
APPLICATION:
Mains enclosed in conduit, buried or underground
ducts for industrial plants, buildings and transformers
where not subject to mechanical damage.